SDO 4xDC 24V 0.5A
Error
Behavior of the diagnostic mes-
sages
Error recovery
Short circuit
n
The test pulses are no longer
detected on the output.
n
e.g. the set test pulse length is too
small
The error is only a short time reported
since with disabling the output no
more testing is possible.
Correct the wiring or configuration
error.
Acknowledge the error and perform a
power cycle.
Cross circuit
n
At an output the wrong test pulses
are detected.
n
e.g. wiring error
The error is only a short time reported
since with disabling the output no
more testing is possible.
Correct the wiring error.
Acknowledge the error and perform a
power cycle.
Wire break error
n
With enabled output, no current >
30mA could be determined.
The error is only a short time reported
since with disabling the output no
more testing is possible.
Correct the wiring or configuration
error.
Acknowledge the error and perform a
power cycle.
Read back error of the output part
n
The target state does not match its
current state.
n
Either external power supply DC
24V and output should be 0 or
external short circuit to ground and
output should be 1.
Error at external power supply is per-
manently reported.
A short circuit or defect of the module
is only a short time reported.
Correct the wiring error.
Acknowledge the error and perform a
power cycle.
The address switch for F-address was
changed
n
The address switch and the con-
figuration was changed.
n
e.g. module replacement
Error is permanently reported.
‘Changing the F-address’ page 72
Perform a power cycle.
Other errors
n
Error in configuration
Error is permanently reported.
Correct the configuration data such as
a wrong F-address.
Perform a power cycle.
Other errors
n
"Light" internal errors
Error is permanently reported.
Perform a power cycle.
Other errors
n
"Heavy" internal errors
An error can not be reported. The
System SLIO Safety module switches
into safe mode and then becomes
inactive.
Perform a power cycle.
VIPA System SLIO
Deployment
Diagnostics > Fault diagnostics
HB300 | SM-S | 02x-1SD10 | en | 20-02