Sub-
index
Name
Description /
Range of values
Type
Bit
Offset
Access Default
16
Parameter change mode
0: Normal parameter record
set
1: Parameter change F-
address
BOOL
1
77
rw
0
17
Activation
Diagnostic interrupt
0: deactivated
1: activated
Bit is not security relevant.
BOOL
1
78
rw
1
19
Channel 0:
Test pulse length in μs
Condition: Channel 0, 1 acti-
vation on "activated"
Different values selectable
(1ms, 1.5ms, 2ms,
2.5ms, ... ,10ms)
BOOL
16
80
rw
1000
20
Channel 1:
Test pulse length in μs
Condition: Channel 0, 1 acti-
vation on "activated"
Different values selectable
(1ms, 1.5ms, 2ms,
2.5ms, ... ,10ms)
BOOL
16
96
rw
1000
21
Channel 2:
Test pulse length in μs
Condition: Channel 2, 3 acti-
vation on "activated"
Different values selectable
(1ms, 1.5ms, 2ms,
2.5ms, ... ,10ms)
UINT
16
112
rw
1000
22
Channel 3:
Test pulse length in μs
Condition: Channel 2, 3 acti-
vation on "activated"
Different values selectable
(1ms, 1.5ms, 2ms,
2.5ms, ... ,10ms)
UINT
16
128
rw
1000
1) Deactivation of channel groups deviates from "normal operation" and represents a potentially dangerous condition.
The version identifier is specific to a module type, i.e. for the input module and the output
module. Since these have different parameter data, in each case with version 0x0001 is
started.
In the MX file, the identifier 0x0000 is entered so that the firmware can
recognize that this is an invalid parametrization. The safety IO module
must not start up with the default values stored in the MX file.
Unique module identifier, which is also used e.g. in the ESI file.
For a valid parametrization this parameter must be set to 0 (default value). If the F-
address is to be changed for a System SLIO safety module, you can delete the F-address
in the memory of the System SLIO safety module by setting this parameter.
‘Setting the F-address’ page 71
Version identifier of the
parametrization data
structure
Module type identifier
Parameter change mode
VIPA System SLIO
Product description
SDO 4xDC 24V 0.5A - FSoE Parameter record set > FSoE application parameters
HB300 | SM-S | 02x-1SD10 | en | 20-02