n
Report cause of STOP
–
Activate this parameter, if the CPU should report the cause of STOP to PG
respectively OP on transition to STOP.
n
Number of messages in the diagnostics buffer
–
This parameter is ignored. The CPU always has a diagnostics buffer (circular
buffer) for 100 diagnostics messages.
n
Synchronization type
–
Here you specify whether clock should synchronize other clocks or not.
–
as slave: The clock is synchronized by another clock.
–
as master: The clock synchronizes other clocks as master.
–
none: There is no synchronization
n
Time interval
–
Time intervals within which the synchronization is to be carried out.
n
Correction factor
–
Lose or gain in the clock time may be compensated within a 24 hour period by
means of the correction factor in ms.
–
If the clock is 1s slow after 24 hours, you have to specify a correction factor of
"+1000" ms.
n
Level of protection
–
Here 1 of 3 protection levels may be set to protect the CPU from unauthorized
access.
–
Protection level 1 (default setting):
No password adjustable, no restrictions
–
Protection level 2 with password:
Authorized users: read and write access
Unauthorized user: read access only
–
Protection level 3:
Authorized users: read and write access
Unauthorized user: no read and write access
5.8.3 Parameters for MPI/DP
The properties dialog of the MPI interface is opened via a double click to the sub module
MPI/DP.
n
Short description: Here the short description "MPI/DP" for the MPI interface is speci-
fied.
n
Order no.: Nothing is shown here.
n
Name: At
Name
"MPI/DP" for the MPI interface is shown. If you change the name, the
new name appears in the Siemens SIMATIC Manager.
n
Type: Please regard only the type "MPI" is supported by the VIPA CPU.
n
Interface: Here the MPI address is shown.
n
Properties: With this button the properties of the MPI interface may be preset.
n
Comment: You can enter the purpose of the MPI interface.
n
Diagnostics: A diagnostics address for the MPI interface is to be preset here. In the
case of an error the CPU is informed via this address.
n
Operating mode, Configuration, Clock: These parameters are not supported.
Diagnostics/Clock
Protection
General
Address
System 300S
+
Deployment CPU 315-4PN23
Setting standard CPU parameters > Parameters for MPI/DP
HB140 | CPU | 315-4PN23 | en | 18-02
47
Содержание SPEED7 300S+ CPU 315PN
Страница 1: ...CPU 315 4PN23 Manual HB140 CPU 315 4PN23 en 18 02 System 300S SPEED7 CPU 315PN...
Страница 89: ...System 300S Deployment PtP communication Modbus Example communication HB140 CPU 315 4PN23 en 18 02 89...
Страница 155: ...Appendix System 300S Appendix HB140 CPU 315 4PN23 en 18 02 155...