n
Proof the correct fixing of the lead isolation.
–
Data lines must be shielded.
–
Analog lines must be shielded. When transmitting signals with small amplitudes
the one sided laying of the isolation may be favourable.
–
Cables for frequency inverters, servo and stepper motors must be shielded.
–
Lay the line isolation extensively on an isolation/protected earth conductor rail
directly after the cabinet entry and fix the isolation with cable clamps.
–
Make sure that the isolation/protected earth conductor rail is connected impe-
dance-low with the cabinet.
–
Use metallic or metallised plug cases for isolated data lines.
n
In special use cases you should appoint special EMC actions.
–
Consider to wire all inductivities with erase links.
–
Please consider luminescent lamps can influence signal lines.
n
Create a homogeneous reference potential and ground all electrical operating sup-
plies when possible.
–
Please take care for the targeted employment of the grounding actions. The
grounding of the PLC serves for protection and functionality activity.
–
Connect installation parts and cabinets with your PLC in star topology with the
isolation/protected earth conductor system. So you avoid ground loops.
–
If there are potential differences between installation parts and cabinets, lay suffi-
ciently dimensioned potential compensation lines.
Electrical, magnetically and electromagnetic interference fields are weakened by means
of an isolation, one talks of absorption. Via the isolation rail, that is connected conductive
with the rack, interference currents are shunt via cable isolation to the ground. Here you
have to make sure, that the connection to the protected earth conductor is impedance-
low, because otherwise the interference currents may appear as interference cause.
When isolating cables you have to regard the following:
n
If possible, use only cables with isolation tangle.
n
The hiding power of the isolation should be higher than 80%.
n
Normally you should always lay the isolation of cables on both sides. Only by means
of the both-sided connection of the isolation you achieve high quality interference
suppression in the higher frequency area. Only as exception you may also lay the iso-
lation one-sided. Then you only achieve the absorption of the lower frequencies. A
one-sided isolation connection may be convenient, if:
–
the conduction of a potential compensating line is not possible.
–
analog signals (some mV respectively µA) are transferred.
–
foil isolations (static isolations) are used.
n
With data lines always use metallic or metallised plugs for serial couplings. Fix the
isolation of the data line at the plug rack. Do not lay the isolation on the PIN 1 of the
plug bar!
n
At stationary operation it is convenient to strip the insulated cable interruption free
and lay it on the isolation/protected earth conductor line.
n
To fix the isolation tangles use cable clamps out of metal. The clamps must clasp the
isolation extensively and have well contact.
n
Lay the isolation on an isolation rail directly after the entry of the cable in the cabinet.
Lead the isolation further on to your PLC and don't lay it on there again!
CAUTION!
Please regard at installation!
At potential differences between the grounding points, there may be a
compensation current via the isolation connected at both sides.
Remedy: Potential compensation line
Isolation of conductors
System 300S
+
Assembly and installation guidelines
Installation guidelines
HB140 | CPU | 315-4PN23 | en | 18-02
21
Содержание SPEED7 300S+ CPU 315PN
Страница 1: ...CPU 315 4PN23 Manual HB140 CPU 315 4PN23 en 18 02 System 300S SPEED7 CPU 315PN...
Страница 89: ...System 300S Deployment PtP communication Modbus Example communication HB140 CPU 315 4PN23 en 18 02 89...
Страница 155: ...Appendix System 300S Appendix HB140 CPU 315 4PN23 en 18 02 155...