4.
Choose if necessary the known MAC address of the list of found stations. To check
this with [Blink] you may cause the MT LED to blink.
5.
Either type in the IP configuration like IP address, subnet mask and gateway. Or
your station is automatically provided with IP parameters by means of a DHCP
server. Depending of the chosen option the DHCP server is to be supplied with
MAC address, equipment name or client ID. The client ID is a numerical order of
max. 63 characters. The following characters are allowed: "hyphen", 0-9, a-z, A-Z
6.
Confirm with [Assign IP configuration].
Directly after the assignment the PROFINET IO controller is online reach-
able using the set IP address data.
Since the IP address data, which were assigned here, are deleted at
PowerOFF, you have to take them to a project by means of the hardware
configuration.
8.8 Hardware configuration - CPU
The configuration of the CPU takes place at the Siemens
‘hardware configurator’
. The
hardware configurator is part of the Siemens SIMATIC Manager. It serves for project engi-
neering. The modules, which may be configured here are listed in the hardware catalog.
If necessary you have to update the hardware catalog with
‘Options
è
Update Catalog’
.
For project engineering a thorough knowledge of the Siemens SIMATIC Manager and the
Siemens hardware configurator is required.
To be compatible with the Siemens SIMATIC Manager the following steps should be exe-
cuted:
1.
Start the Siemens hardware configurator with a new project.
2.
Insert a profile rail from the hardware catalog.
3.
Place at
‘Slot’
-Number 2 the CPU 315-2 PN/DP (6ES7 315-2EH14-0AB0 V3.2).
4.
The integrated PROFIBUS DP master (X3) is to be configured and connected via
the sub module X1 (MPI/DP). In the operation mode PROFIBUS the CPU may fur-
ther more be accessed via the MPI interface (X2) with address 2 und 187.5kbit/s.
5.
The PROFINET IO controller is to be configured via the sub module
‘X2 PN-IO’
.
Open the property window of the internal PROFINET IO controller via double-click on the
component PN-IO:
1.
At
‘General’
enter a
device name
. The device name on the Ethernet subnet must
be unique.
2.
For the PROFINET IO controller enter the
IP address
,
subnet mask
and
gateway
and select the wanted
subnet.
Precondition
Proceeding
Parametrization of the IP
address data for the
PROFINET IO controller
System 300S
+
Deployment Ethernet communication - productive
Hardware configuration - CPU
HB140 | CPU | 315-4PN23 | en | 18-02
109