![YASKAWA SI-EM3 Скачать руководство пользователя страница 70](http://html.mh-extra.com/html/yaskawa/si-em3/si-em3_installation-manual_907104070.webp)
70
YASKAWA
TOEP C730600 91B Modbus TCP/IP Installation Manual
A - Braided shield cable
B - Metal panel
C - Cable clamp (conductive)
Figure 10.4 Ground Area
11
Specifications
◆
Specifications
Table 11.1 Option Specifications
Items
Specifications
Model
SI-EM3
Supported Messages
•
Read Multiple Registers (03 (Hex.))
•
Write Single Register (06 (Hex.))
•
Write Multiple Registers (10 (Hex.))
•
Read and Write Registers (17 (Hex.))
Commands that support multiple registers have a maximum Read and Write
size of 16 registers.
Modbus TCP/IP Specifications
Modbus-IDA Passed
Recommended Connector Type
Shielded Cat5e cable
Physical Layer Type
Ethernet Isolated Physical Layer
IP Address Setting
Programmable from drive keypad or network
Communication Speed
Programmable from drive keypad or network: 10/100 Mbps, auto-negotiate.
Number of Connections
•
Modbus TCP/IP: 10
•
Web page connections: 2
Duplex Mode
•
Half/Half
•
Auto-negotiate
•
Full/Full
Address Startup Mode
•
Static
•
BOOTP