TOEP C730600 91B Modbus TCP/IP Installation Manual
59
Note:
•
You can write the EEPROM to the drive a maximum of 100,000 times. Do not frequently execute the Enter
command (0900 (Hex.)) that is written to EEPROM. When the command data or broadcast message is
transmitted to the drive, the Enter command is not necessary.
•
Parameter data cannot be written to EEPROM during undervoltage, even using 0900 (Hex.).
•
If undervoltage occurs when a making several parameter changes issued with a single ENTER command, the
writing process may be aborted before all of the new changes have been written. Because all of the data has
not yet been written, the EEPROM data error
CPF06
will be displayed the next time power to the drive is
cycled. To prevent
CPF06
, wait approximately 5 seconds after issuing the ENTER command before shutting
off drive power.
■
Enter Command Function Differences Depending on the Setting of H5-11
Table 7.5 Enter Command Function Differences Depending on the Setting of H5-11
H5-11 Settings
H5-11 = 0
H5-11 = 1
Time when the
parameter settings
are enabled
When the drive receives the Enter command
from the master
When you change the parameter settings
Upper and lower
limit check
Checks the upper and lower limits and
considers the related parameter settings.
Checks the upper and lower limit of the
changed parameter only.
Default setting of
related parameters
Not affected. The settings of related
parameters remain unchanged. They must be
changed manually, if needed.
Automatically changes the default settings
for the related parameters.
Fault detection when
you set more than
one parameter
Accepts and responds as usual to correct
setting data if the data contains parameter
setting errors. The drive discards the
disabled setting data, but will not return an
error message.
Error occurs if only one setting is invalid.
All data sent are discarded. The drive
discards the data that was sent.
8
Web Interface
The option contains a series of web pages that allow for viewing of status and diagnostic
information through a standard web browser. The embedded web pages include:
•
Home Page
•
Modbus-TCP Page
•
Network Page
◆
Home Page
The Home page shows the status of the drive and the I/O. It also shows identifying
information about the drive and the option.