![YASKAWA SI-EM3 Скачать руководство пользователя страница 54](http://html.mh-extra.com/html/yaskawa/si-em3/si-em3_installation-manual_907104054.webp)
54
YASKAWA
TOEP C730600 91B Modbus TCP/IP Installation Manual
Register Number
(Hex.)
Description
0002
Frequency Reference
Units are determined by parameter
o1-03 [Frequency
Display Unit Selection]
.
0003
Output voltage gain
Unit: 0.1%
Setting range: 20 (2.0%) - 2000 (200.0%),
the default value at energize: 1000 (100.0%)
0004
Torque reference/torque limit (0.1% signed)
0005
Torque compensation (0.1% signed)
0006
PID setpoint (0.01% signed)
0007
Multi-Function Analog Output Terminal 1 Setting (10 V / 4000 (Hex.))
0008
Multi-Function Analog Output Terminal 2 Setting (10 V / 4000 (Hex.))
0009
MFDO setting
bit 0
Multi-Function Contact Output 1
Terminal M1-M2 (varies by drive model)
bit 1
Multi-Function Contact Output 2
Terminal M3-M4 (varies by drive model)
bit 2
Multi-Function Contact Output 3
Terminal M5-M6 (varies by drive model)
bit 3- 5
Reserved
bit 6
Enables the function in bit 7
bit 7
Fault Relay Output
Terminal MA/MB-MC (varies by drive model)
bit 8 - F
Reserved
000A
Pulse train output (Units: 1/1 Hz, setting range: 0 - 32000)
000B - 000E
Reserved
000F
Command selection setting
bit 0
Reserved
bit 1
Input for the PID setpoint
bit 2
Torque reference/torque limit input (enables the setting
from MEMOBUS/Modbus)