22
YASKAWA
TOEP C730600 91B Modbus TCP/IP Installation Manual
A - Route wires through the openings
provided on the left side of the
front cover.
B - Use the open space provided
inside the drive to route option
wiring.
Figure 5.6 Wire Routing Examples
*1
If there is wiring outside the enclosure, the drive will not meet Enclosed wall-mounted
type (IP20/UL Type 1) requirements.
6.
Firmly connect the Ethernet communication cable to the option modular
connector (CN1).
Isolate communication cables from main circuit wiring and other electrical and
power lines. Make sure that you firmly connect the cable end. (Refer to
). Refer to
Communication Cable Specifications on page 42
for more
information.
NOTICE
Damage to Equipment. When you touch the option, make sure that
you observe correct electrostatic discharge (ESD) procedures. If you do not follow
procedures, it can cause ESD damage to the drive circuitry.
7.
Reattach the front cover (A), terminal cover (C), and keypad (B).
Refer to the drive manuals for more information.
NOTICE
Do not pinch cables between the front covers and the drive. Failure to
comply could cause erroneous operation.