![YASKAWA SI-EM3 Скачать руководство пользователя страница 50](http://html.mh-extra.com/html/yaskawa/si-em3/si-em3_installation-manual_907104050.webp)
50
YASKAWA
TOEP C730600 91B Modbus TCP/IP Installation Manual
No.
(Hex.)
Name
Description
Default
(Range)
4 : Half/Full
5 : Auto/Half
6 : Auto/Full
7 : Full/Half
8 : Full/Auto
Note:
•
When you set this parameter to
0
,
2
,
3
,
4
,
7
, or
8
, you
must also set
F7-15 [Communication Speed Selection]
.
•
The option sets the duplex mode as specified by these
F7-14
settings:
–
0: Half/Half, 3: Half/Auto, 4: Half/Full, duplex mode is
"Half".
–
1: Auto/Auto, 5: Auto/Half, 6: Auto/Full, duplex mode
is "Auto".
–
2: Full/Full, 7: Full/Half, 8: Full/Auto, duplex mode is
"Full".
F7-15
(03F3)
Communication
Speed Selection
Sets the communications speed.
10 : 10/10 Mbps
100 : 100/100 Mbps
101 : 10/100 Mbps
102 : 100/10 Mbps
Note:
•
F7-15
is only effective when the port is set to half or full
duplex in
F7-14 [Duplex Mode Selection]
.
•
The default setting and setting range are different for
different product series.
–
1000-Series, GA700, GA800, CR700, CH700 Drives
Default value: 10
Range: 10 - 102
–
GA500
Default value: 10
Range: 10, 100
–
HV600, FP605
Default value: 10
Range: 10, 102
•
This option sets the communication speed as specified by
these
F7-15
settings:
–
10: 10/10 Mbps or 101: 10/100 Mbps, the speed is 10
Mbps.
–
100: 100/100 Mbps or 102: 100/10 Mbps, the speed is
100 Mbps.
10