![YASKAWA SI-EM3 Скачать руководство пользователя страница 51](http://html.mh-extra.com/html/yaskawa/si-em3/si-em3_installation-manual_907104051.webp)
YASKAWA
TOEP C730600 91B Modbus TCP/IP Installation Manual
51
No.
(Hex.)
Name
Description
Default
(Range)
F7-16
(03F4)
Timeout Value
Sets the detection time for a communications timeout.
Note:
•
Set this parameter to
0.0
to disable the connection
timeout function.
•
This parameter is not available in all 1000-series drives.
•
Changes to this parameter take effect immediately. It is
not necessary to cycle power on the drive.
0.0 s
(0.0 s - 30.0 s)
H5-11
(043C)
Communications
ENTER Function
Selection
(Function
common to
communication
option)
Sets when an Enter command is necessary to use MEMOBUS/
Modbus communications to change parameter values.
0 : Parameter changes are activated when ENTER command is
written
1 : Parameter changes are activated immediately. No ENTER
command is necessary.
0
(0, 1)
Table 6.1 Option Monitor
No.
Name
Description
Range
U6-80 - U6-83
Option IP Address 1 - 4
Shows the currently available local IP
Address.
•
U6-80
: First octet
•
U6-81
: Second octet
•
U6-82
: Third octet
•
U6-83
: Forth octet
0 - 255
U6-84 - U6-87
Online Subnet 1 - 4
Shows the currently available subnet
mask.
•
U6-84
: First octet
•
U6-85
: Second octet
•
U6-86
: Third octet
•
U6-87
: Forth octet
0 - 255
U6-88 - U6-91
Online Gateways 1 - 4
Shows the currently available gateway
address.
•
U6-88
: First octet
•
U6-89
: Second octet
•
U6-90
: Third octet
•
U6-91
: Forth octet
0 - 255
U6-92
Online Speed
Shows link speed currently available.
10: 10 Mbps
100: 100
Mbps
U6-93
Online Duplex
Shows duplex setting currently available.
0: Half/Half
1: Full/Full