![YASKAWA SI-EM3 Скачать руководство пользователя страница 57](http://html.mh-extra.com/html/yaskawa/si-em3/si-em3_installation-manual_907104057.webp)
YASKAWA
TOEP C730600 91B Modbus TCP/IP Installation Manual
57
No. (Modbus
Register)
Drive
Registers
Register Name
Bit
Description
E
Dynamic Braking Transistor Fault (rr)
F
Braking Resister Overheat (rH)
200A
C1
Error Signal 2
0
External Fault 3, input terminal S3 (EF3)
1
External Fault 4, input terminal S4 (EF4)
2
External Fault 5, input terminal S5 (EF5)
3
External Fault 6, input terminal S6 (EF6)
4
External Fault 7, input terminal S7 (EF7)
5
External Fault 8, input terminal S8 (EF8)
6
Cooling fan Error (FAn)
7
Overspeed (oS)
8
Excessive Speed Deviation (dEv)
9
PG Disconnected (PGo)
A
Input Phase Loss (PF)
B
Output Phase Loss (LF)
C
Motor Overheat (PTC input) (oH3)
D
Digital Operator Connection Fault (oPr)
E
EEPROM Write Error (Err)
F
Motor Overheat Fault (PTC input) (oH4)
200B
C2
Error Signal 3
0
MEMOBUS/Modbus Communication Error
(CE)
1
Option Communication Error (bUS)
2
Reserved
3
Reserved
4
Control Fault (CF)
5
Zero Servo Fault (SvE)
6
Option External Fault (EF0)
7
PID Feedback Loss (FbL)