TOEP C730600 91B Modbus TCP/IP Installation Manual
No.
(Hex.)
Name
Description
Default
(Range)
Note:
•
This parameter is only effective when
F7-13 = 0
[Address Mode at Startup = Static]
.
•
All IP Addresses must be unique.
•
You must cycle power to the drive for the changes to
take effect. For non-1000 series drives, you can set
F6-
15 = 1 [Comm. Option Parameters Reload = Reload
Now]
.
F7-06
(03EA)
Subnet Mask 2
Sets the static/fixed Subnet Mask. Sets the second most
significant octet.
Note:
•
This parameter is only effective when
F7-13 = 0
[Address Mode at Startup = Static]
.
•
All IP Addresses must be unique.
•
You must cycle power to the drive for the changes to
take effect. For non-1000 series drives, you can set
F6-
15 = 1 [Comm. Option Parameters Reload = Reload
Now]
.
255
(0 - 255)
F7-07
(03EB)
Subnet Mask 3
Sets the static/fixed Subnet Mask. Sets the third most
significant octet.
Note:
•
This parameter is only effective when
F7-13 = 0
[Address Mode at Startup = Static]
.
•
All IP Addresses must be unique.
•
You must cycle power to the drive for the changes to
take effect. For non-1000 series drives, you can set
F6-
15 = 1 [Comm. Option Parameters Reload = Reload
Now]
.
255
(0 - 255)
F7-08
(03EC)
Subnet Mask 4
Sets the static/fixed Subnet Mask. Parameter F7-08 sets the
fourth most significant octet.
Note:
•
This parameter is only effective when
F7-13 = 0
[Address Mode at Startup = Static]
.
•
All IP Addresses must be unique.
•
You must cycle power to the drive for the changes to
take effect. For non-1000 series drives, you can set
F6-
15 = 1 [Comm. Option Parameters Reload = Reload
Now]
.
0
(0 - 255)
F7-09
(03ED)
Gateway Address
1
Sets the static/fixed Gateway address. Sets the most significant
octet.
Note:
•
This parameter is only effective when
F7-13 = 0
[Address Mode at Startup = Static]
.
•
All IP Addresses must be unique.
•
You must cycle power to the drive for the changes to
take effect. For non-1000 series drives, you can set
F6-
192
(0 - 255)