TOEP C730600 91B Modbus TCP/IP Installation Manual
No. (Modbus
Register)
Drive
Registers
Register Name
Bit
Description
C
Reserved
D
Reserved
E
ComRef status/ NetRef status
F
ComCtrl status/ NetCtrl status
2001
44
Motor Speed Monitor (U1-05)
2002
48
Torque Reference Monitor (U1-09)
2003
F0
PG Count Channel 1
2004
40
Frequency Reference Monitor (U1-01)
2005
41
Output Frequency Monitor (U1-02)
2006
26
Output Current (U1-03) (units: 0.1 A)
2007
4F
Terminal A2 Input Level Monitor (U1-14)
2008
46
DC Bus Voltage Monitor (U1-07)
2009
C0
Error Signal 1
0
Reserved
1
Undervoltage (Uv1)
2
Control Power Supply Undervoltage (Uv2)
3
Soft Charge Circuit Fault (Uv3)
4
Short Circuit/IGBT Failure (SC)
5
Ground Fault (GF)
6
Overcurrent (oC)
7
Overvoltage (ov)
8
Heatsink Overheat (oH)
9
Heatsink Overheat (oH1)
A
Motor Overload (oL1)
B
Drive Overload (oL2)
C
Overtorque Detection 1 (oL3)
D
Overtorque Detection 2 (oL4)