2.2.3 Installation Site
Take the following precautions at the installation site.
Situation
Installation Precaution
Installation in a Control
Panel
Design the control panel size, unit layout, and cooling method so the
temperature around the Servopack does not exceed 55
°
C.
Installation Near a
Heating Unit
Minimize heat radiated from the heating unit as well as any tempera-
ture rise caused by natural convection so the temperature around the
Servopack does not exceed 55
°
C.
Installation Near a
Source of Vibration
Install a vibration isolator beneath the Servopack to avoid subjecting
it to vibration.
Installation at a Site
Exposed to Corrosive
Gas
Corrosive gas does not have an immediate effect on the Servopack,
but will eventually cause electronic components and contactor-related
devices to malfunction. Take appropriate action to avoid corrosive
gas.
Other Situations
Do not install the Servopack in hot and humid locations or locations
subject to excessive dust or iron powder in the air.
2.2.4 Orientation
Install the Servopack perpendicular to the wall as shown in the figure. The Servopack must be
oriented this way because it is designed to be cooled by natural convection or cooling fan.
Secure the Servopack using 2 to 4 mounting holes. The number of holes dependson the capacity.