Duplex System: Single Transducer Connection using Analog Input A2
A2 used for pressure transducer.
Set Jumper S1 to the “I” Position (4-20 mA) for both iQpump drives (default).
V
I
A1 A2 A3
Jumper S1
AC
A2
E(G)
Control
Terminal
Block
Drive 2
+ -
V+
4-20 mA
Outlet
Transducer
Output
AC
A2
E(G)
Control
Terminal
Block
Drive 1
External 24 Vdc
Power Supply
Triplex System: Transducer Connection using Analog Input A2
A2 used for water level or suction pressure transducer.
Set jumper S1 to the “I” position for the last iQpump drive on the network.
All other iQpump drives should have S1 set to the “V” position.
V
I
A1 A2 A3
Jumper S1
V
I
A1 A2 A3
Jumper S1
V
I
A1 A2 A3
Jumper S1
AC
A2
E(G)
Control
Terminal
Block
Drive 2
+ -
V+
4-20 mA
Transducer
Output
AC
A2
E(G)
Control
Terminal
Block
Drive 1
External 24 Vdc
Power Supply
AC
A2
E(G)
Control
Terminal
Block
Drive X
Last drive on network
i.4 Electrical Installation
42
YASKAWA TOEP YAIP1W 02E YASKAWA AC Drive - iQpump1000 Installation & Start-up Guide