No.
Parameter Name
Setting Range
Default
C1-01
Acceleration Time 1
0.0 to 6000.0 s
10.0 s
C1-02
Deceleration Time 1
C1-03
Acceleration Time 2
C1-04
Deceleration Time 2
is set in units of 0.01 s (C1-10 = 0), the setting range becomes 0.00 to 600.00 s.
n
E2-01: Motor Rated Current
Provides motor control, protects the motor, and calculates torque limits. Set E2-01 to the full load amps (FLA) stamped on
the motor nameplate. If Auto-Tuning completes successfully, the value entered to T1-04 will automatically be saved to E2-01.
No.
Parameter Name
Setting Range
Default
E2-01
Motor Rated Current
10% to 200% of the drive
rated current
Determined by
o2-04
<1> Display is in the following units:
Note:
An oPE02 error will occur if E2-01
≤
E2-03. Set E2-03 correctly to prevent this error.
n
E2-04: Number of Motor Poles
Set the number of motor poles to E2-04. If Auto-Tuning completes successfully, the value entered to T1-06 will automatically
be saved to E2-04.
No.
Parameter Name
Setting Range
Default
E2-04
Number of Motor Poles
2 to 48
2
n
H1-01 to H1-08: Functions for Terminals S1 to S8
.
No.
Parameter Name
Setting
Range
Default
H1-01
Multi-Function Digital Input Terminal S1 Function Selection
1 to 9F
40 (F)
: Forward Run Command (2-Wire sequence)
H1-02
Multi-Function Digital Input Terminal S2 Function Selection
1 to 9F
F: Through Mode
H1-03
Multi-Function Digital Input Terminal S3 Function Selection
0 to 9F
26: External Pump Fault
H1-04
Multi-Function Digital Input Terminal S4 Function Selection
0 to 9F
14: Fault Reset
H1-05
Multi-Function Digital Input Terminal S5 Function Selection
0 to 9F
H1-06
Multi-Function Digital Input Terminal S6 Function Selection
0 to 9F
H1-07
Multi-Function Digital Input Terminal S7 Function Selection
0 to 9F
H1-08
Multi-Function Digital Input Terminal S8 Function Selection
0 to 9F
Table i.22 Multi-Function Digital Input Terminal Settings
Setting
Function
Page
0
3-Wire sequence
–
2
External Reference 1/2 Selection
–
3
Multi-Step Speed Reference 1
–
4
Multi-Step Speed Reference 2
–
5
Multi-Step Speed Reference 3
–
6
Jog reference selection
–
7
Accel/decel time selection 1
–
8
Baseblock command (N.O.)
–
Setting
Function
Page
9
Baseblock command (N.C.)
–
A
Accel/decel ramp hold
–
B
Drive overheat alarm (oH2)
–
C
Analog terminal input selection
–
F
Through mode
–
10
Up command
–
11
Down command
–
12
Forward Jog
–
i.5 Start-Up Programming and Operation
YASKAWA TOEP YAIP1W 02E YASKAWA AC Drive - iQpump1000 Installation & Start-up Guide
59
Содержание CIMR-PW*A Series
Страница 113: ......