Drive Model
Wire Gauge (AWG, kcmil)
Screw
Size
Crimp
Terminal
Model
Number
Tool
Insulation
Cap Model
No.
R/L1, S/L2, T/L3 U/T1, V/T2, W/T3
Machine No.
Die Jaw
4A1200
4/0 × 8P
M12
100-L12
YF-1
YET-300-1
TD-324,
TD-312
TP-100
100-051-560
250 × 8P
150-L12
TD-325,
TD-313
TP-150
100-051-562
300 × 8P
Note:
Use crimp insulated terminals or insulated shrink tubing for wiring connections. Wires should have a continuous maximum allowable
temperature of 75 °C 600 Vac UL-approved vinyl-sheathed insulation.
Factory Recommended Branch Circuit Protection for UL Compliance
NOTICE: If a fuse is blown or a Ground Fault Circuit Interrupter (GFCI) is tripped, check the wiring and the selection of the peripheral devices.
Check the wiring and the selection of peripheral devices to identify the cause. Contact Yaskawa before restarting the drive or the peripheral
devices if the cause cannot be identified.
Yaskawa recommends installing one of the following types of branch circuit protection to maintain compliance with UL508C.
Semiconductor protective type fuses are preferred. Alternate branch circuit protection devices are also listed in the tables
below.
Table i.27 Factory Recommended Drive Branch Circuit Protection (Normal Duty)
Drive Model
Normal Duty
Nominal
Output Power
HP
AC Drive Input
Amps
MCCB Rating
Amps
Time Delay Fuse
Non-time Delay
Fuse Rating
Bussmann Semi-
conductor Fuse
Rating (Fuse
200 V Class
2A0004
0.75
3.9
15
6.25
10
FWH-70B (70)
2A0006
1 - 1.5
7.3
15
12
20
FWH-70B (70)
2A0008
2
8.8
15
15
25
FWH-70B (70)
2A0010
3
10.8
20
17.5
30
FWH-70B (70)
2A0012
3
13.9
25
20
40
FWH-70B (70)
2A0018
5
18.5
35
30
50
FWH-90B (90)
2A0021
7.5
24
45
40
70
FWH-90B (90)
2A0030
10
37
60
60
110
FWH-100B (100)
2A0040
15
52
100
90
150
FWH-200B (200)
2A0056
20
68
125
110
200
FWH-200B (200)
2A0069
25
80
150
125
225
FWH-200B (200)
2A0081
30
96
175
150
275
FWH-300A (300)
2A0110
40
111
200
175
300
FWH-300A (300)
2A0138
50
136
250
225
400
FWH-350A (350)
2A0169
60
164
300
250
450
FWH-400A (400)
2A0211
75
200
400
350
600
FWH-400A (400)
2A0250
100
271
500
450
800
FWH-600A (600)
2A0312
125
324
600
500
800
FWH-700A (700)
2A0360
150
394
700
600
1000
FWH-800A (800)
2A0415
175
471
900
800
1400
FWH-1000A (1000)
400 V Class
4A0002
1
2.1
15
3.5
6
FWH-40B (40)
4A0004
2
4.3
15
7.5
12
FWH-50B (50)
4A0005
3
5.9
15
10
17.5
FWH-70B (70)
i.9 Standards Compliance
YASKAWA TOEP YAIP1W 02E YASKAWA AC Drive - iQpump1000 Installation & Start-up Guide
107
Содержание CIMR-PW*A Series
Страница 113: ......