Drive Model
Normal Duty
Nominal
Output Power
HP
AC Drive Input
Amps
MCCB Rating
Amps
Time Delay Fuse
Non-time Delay
Fuse Rating
Amps
Bussmann Semi-
conductor Fuse
Rating (Fuse
4A0007
3
8.1
15
12
20
FWH-70B (70)
4A0009
5
9.4
15
15
25
FWH-90B (90)
4A0011
7.5
14
25
20
40
FWH-90B (90)
4A0018
10
20
40
35
60
FWH-80B (80)
4A0023
15
24
45
40
70
FWH-100B (100)
4A0031
20
38
75
60
110
FWH-125B (125)
4A0038
25
44
75
75
125
FWH-200B (200)
4A0044
30
52
100
90
150
FWH-250A (250)
4A0058
40
58
100
100
150
FWH-250A (250)
4A0072
50
71
125
110
200
FWH-250A (250)
4A0088
60
86
150
150
250
FWH-250A (250)
4A0103
75
105
200
175
300
FWH-250A (250)
4A0139
100
142
250
225
400
FWH-350A (350)
4A0165
125
170
300
250
500
FWH-400A (400)
4A0208
150
207
400
350
600
FWH-500A (500)
4A0250
200
248
450
400
700
FWH-600A (600)
4A0296
250
300
600
500
800
FWH-700A (700)
4A0362
300
346
600
600
FWH-800A (800)
4A0414
350
410
800
700
FWH-800A (800)
4A0515
400 - 450
465
900
800
FWH-1000A (1000)
4A0675
500 - 600
657
1200
1100
FWH-1200A (1200)
4A0930
700 - 800
922
Not Applicable
FWH-1200A (1200)
4A1200
900 - 1000
1158
FWH-1600A (1600)
600 V Class
5A0003
2
3.6
15
6.25
10
FWP-50B (50)
5A0004
3
5.1
15
8
15
FWP-50B (50)
5A0006
5
8.3
15
12
20
FWP-60B (60)
5A0009
7.5
12
20
20
35
FWP-60B (60)
5A0011
10
16
30
25
45
FWP-70B (70)
5A0017
15
23
40
40
60
FWP-100B (100)
5A0022
20
31
60
50
90
FWP-100B (100)
5A0027
25
38
75
60
110
FWP-125A (125)
5A0032
30
45
75
75
125
FWP-125A (125)
5A0041
40
44
75
75
125
FWP-175A (175)
5A0052
50
54
100
90
150
FWP-175A (175)
5A0062
60
66
125
110
175
FWP-250A (250)
5A0077
75
80
150
125
225
FWP-250A (250)
5A0099
100
108
175
175
300
FWP-250A (250)
5A0125
125
129
225
225
350
FWP-350A (350)
5A0145
150
158
300
275
450
FWP-350A (350)
5A0192
200
228
400
350
600
FWP-600A (600)
5A0242
250
263
500
450
700
FWP-600A (600)
<1> Maximum MCCB Rating is 15 A, or 200 % of drive input current rating, whichever is larger. MCCB voltage rating must be 600 VAC or greater.
<2> Maximum Time Delay fuse is 175% of drive input current rating. This covers any Class CC, J or T class fuse.
<3> Maximum Non-time Delay fuse is 300% of drive input current rating. This covers any CC, J or T class fuse.
<4> When using semiconductor fuses, Bussman FWH and FWP are required for UL compliance. Select FWH for 200 V Class and 400 V Class models
and FWP fuses for 600 V models.
i.9 Standards Compliance