Drive Model
Terminal
Recomm. Gauge
mm
2
(AWG, kcmil)
Wire Range
mm
2
(AWG, kcmil)
Screw
Size
Tightening Torque
N·m (lb.in.)
5A0125
R/L1, S/L2, T/L3
70
(2/0)
35 to 150
(1 to 300)
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3
70
(2/0)
35 to 150
(1 to 300)
⊖
,
⊕
1
–
70
(2/0 to 3/0)
⊕
3
–
35 to 50
(1 to 1/0)
35
(3)
35 to 150
(3 to 300)
5A0145
R/L1, S/L2, T/L3
95
(3/0)
95 to 150
(2/0 to 300)
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3
95
(3/0)
95 to 150
(2/0 to 300)
⊖
,
⊕
1
–
70 to 95
(3/0 to 4/0)
⊕
3
–
70 to 95
(1/0 to 2/0)
35
(3)
35 to 150
(3 to 300)
5A0192
R/L1, S/L2, T/L3
185
(300)
95 to 300
(2/0 to 600)
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3
150
(250)
95 to 300
(2/0 to 600)
⊖
,
⊕
1
–
95 to 185
(2/0 to 400)
⊕
3
–
95 to 120
(2/0 to 250)
M10
18 to 23
(159 to 204)
50
(1)
35 to 300
(1 to 350)
M12
32 to 40
(283 to 354)
5A0242
R/L1, S/L2, T/L3
240
(400)
95 to 300
(2/0 to 600)
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3
185
(350)
95 to 300
(2/0 to 600)
⊖
,
⊕
1
–
95 to 240
(2/0 to 500)
⊕
3
–
150
(250 to 300)
M10
18 to 23
(159 to 204)
50
(1)
35 to 300
(1 to 350)
M12
32 to 40
(283 to 354)
Note:
When connecting peripheral devices or options to terminals
⊖
,
⊕
1,
⊕
3, B1, and B2 , refer to the instruction manual for each device. For
more information, contact Yaskawa or your nearest sales representative.
u
Main Circuit Terminal and Motor Wiring
This section outlines the various steps, precautions, and checkpoints for wiring the main circuit terminals and motor terminals.
WARNING! Electrical Shock Hazard. Do not connect the AC power line to the output terminals of the drive. Failure to comply could result
in death or serious injury by fire as a result of drive damage from line voltage application to output terminals.
NOTICE: When connecting the motor to the drive output terminals U/T1, V/T2, and W/T3, the phase order for the drive and motor should
match. Failure to comply with proper wiring practices may cause the motor to run in reverse if the phase order is backward.
NOTICE: Route motor leads U/T1, V/T2, and W/T3 separate from all other leads to reduce possible interference related issues. Failure to
comply may result in abnormal operation of drive and nearby equipment.
NOTICE: Do not connect phase-advancing capacitors or LC/RC noise filters to the output circuits. Failure to comply could result in damage
to the drive, phase-advancing capacitors, LC/RC noise filters or ground fault circuit interrupters.
i.4 Electrical Installation
34
YASKAWA TOEP YAIP1W 02E YASKAWA AC Drive - iQpump1000 Installation & Start-up Guide