Table i.13 Voltage/Current Selection Parameter Details
No.
Parameter Name
Description
Setting
Range
Default
Setting
H3-01
Terminal A1 signal level selection
Selects the signal level for terminal A1.
0: 0 to 10 Vdc
1: 0 to 10 Vdc Bipolar
2: 4 to 20 mA
3: 0 to 20 mA
0 to 3
0
H3-05
Terminal A3 signal level selection
Selects the signal level for terminal A3.
0: 0 to 10 Vdc
1: 0 to 10 Vdc Bipolar
2: 4 to 20 mA
3: 0 to 20 mA
0 to 3
0
H3-09
Terminal A2 signal level selection
Selects the signal level for terminal A2.
0: 0 to 10 Vdc
1: 0 to 10 Vdc Bipolar
2: 4 to 20 mA
3: 0 to 20 mA
0 to 3
2
n
Transducer Wiring
Simplex Pump System - Transducer Connection using Analog Input A2 (4 to 20 mA Mode)
A2 used for pressure transducer. Example of retrofit application where an external power supply is used.
Set Jumper S1 to the “I” Position (4-20 mA) for the iQpump drive (default).
V
I
A1 A2 A3
Jumper S1
+ -
V+
4-20 mA
Transducer
Output
AC
A2
E(G)
Control
Terminal
Block
Drive
External 24 Vdc
Power Supply
A2 used for pressure transducer. Example of new application where internal power supply is used
Shield
24V Power Supply
Transducer
Signal 0-10 Vdc
(typical)
Example:
Customer supplied
pressure transducer
feedback device
Supply Common
2
4
3
1
N/C
V+
Output
Com
+
(3-Wire Transducer)
A2
24V
AC
E(G)
Control
Terminal
Block
Drive
Shield
SIG
24V Power Supply
Transducer
Signal 4-20 mA
(typical)
2
4
3
1
N/C
N/C
V+
Output
Example:
Customer supplied
pressure transducer
feedback device
(2-Wire Transducer)
A2
24V
AC
E(G)
Control
Terminal
Block
Drive
i.4 Electrical Installation
YASKAWA TOEP YAIP1W 02E YASKAWA AC Drive - iQpump1000 Installation & Start-up Guide
41