Troubleshooting 3-4
RS232 Communications
The following is a quick reference guide for troubleshooting RS232 serial communications to the E7 drive. Make a copy of the following pages
and check-off each item as it is completed. For detailed information on the RS232 standard please refer to
EIA RS-232-C
. or later revision. For
information on the E7 drive RS232 interface, refer to previous sections of this manual.
1:
For RS232 communications
1.1:
Verify that the correct cable is used to connect the controller to the E7 drive.
1.2:
Verify that the controller is set for RS232 communications and that the communication’s cable is connected to the
correct communications port.
1.3:
Record the controller communications’ parameters
Baud Rate
Parity
Data
Bits
Stop
Bits
Protocol
1.4:
Record the E7 drive communications’ parameters (H5-02, H5-03, H5-07, H5-08)
Baud Rate
Parity
Data
Bits
Stop
Bits
Protocol
1.5:
Verify that the communications’ parameters match.
2:
Check the controller RS232 wiring requirements
2.1:
CTS(Clear to Send)/RTS(Ready to Send) jumper required on the controller end?
2.2:
DTR(Data Terminal ready)/DSR(Data Set Ready)/RLSD(Receive Line Signal Detector) jumper required on the
controller end?
2.3:
TxD(Transmit Data)/RxD(Receive Data) connections are made correctly.
3:
Send a message from the controller to the E7 drive.
3.1:
Connect an oscilloscope between the E7 drive RxD and GND.
3.1.1:
Verify that the message pulse train exists and contains the correct number of pulses. Refer to the chapter
Message Formats for information on the message contents.
3.1.2:
Verify that he signal levels adhere to the RS232 standard.
3.2:
Insert a data analyzer in the RS232 circuit and capture the message sent by the controller in a hexadecimal format.
Record the command message below.
[
] [
] [
] [
] [
] [
] [
] [
] [
] [
]
[
] [
] [
] [
] [
] [
] [
] [
] [
] [
]
[
] [
] [
] [
] [
] [
] [
] [
] [
] [
]
[
] [
] [
] [
] [
] [
] [
] [
] [
] [
]
Содержание CIMR-E7U Series
Страница 1: ...E7 Drive Parameter Access Technical Manual Drive Models CIMR E7U Document Number TM E7 11...
Страница 2: ......
Страница 6: ...iv This page intentionally left blank...
Страница 8: ...Connections 1 2 This page intentionally left blank...
Страница 10: ...Connections 1 4 This page intentionally left blank...
Страница 19: ...Connections 1 13 This page intentionally left blank...
Страница 21: ...Message Formats 2 2 This page intentionally left blank...
Страница 35: ...Troubleshooting 3 2 This page intentionally left blank...
Страница 43: ...Troubleshooting 3 10 This page intentionally left blank...
Страница 45: ...E7 Drive Parameters 4 2 This page intentionally left blank...
Страница 71: ...E7 Drive Parameters 4 28 This page intentionally left blank...
Страница 73: ...User Notes 5 3 This page intentionally left blank...
Страница 81: ...User Notes 5 11 Notes Enter the current application parameter data and any relevant notes...