E7 Drive Parameters 4-14
Prm
Adr
Function
Data
Limits / Selections
Inc
Default
Run Acs
Dep
d1-01 0280h
Reference 1
0.0 ~ 400.0 Hz
0.01 Hz
0.0 Hz
Run A o2-09*
d1-02 0281h
Reference 2
0.0 ~ 400.0 Hz
0.01 Hz
0.0 Hz
Run A
d1-03 0282h
Reference 3
0.0 ~ 400.0 Hz
0.01 Hz
0.0 Hz
Run A
d1-04 0283h
Reference 4
0.0 ~ 400.0 Hz
0.01 Hz
0.0 Hz
Run A
d1-17 0292h
Jog Reference
0.0 ~ 400.0 Hz
0.01 Hz
6.0 Hz
Run A
d2-01 0289h
Ref Upper Limit
0.0 ~ 110.0 %
0.10% 100.00%
A
d2-02 028Ah Ref Lower Limit
0.0 ~ 110.0 %
0.10% 0.00%
A
d2-03 0293h Ref1 Lower Limit
0.0 ~ 110.0 %
0.10% 0.00%
A
d3-01 0294h
Jump Freq 1
0.0 ~ 200.0 Hz
0.1 Hz
0.0 Hz
A
d3-02 0295h
Jump Freq 2
0.0 ~ 200.0 Hz
0.1 Hz
0.0 Hz
A
d3-03 0296h
Jump Freq 3
0.0 ~ 200.0 Hz
0.1 Hz
0.0 Hz
A
d3-04 0297h
Jump Bandwidth
0.0 ~ 20.0 Hz
0.1 Hz
1.0 Hz
A
d4-01 0298h MOP Ref Memory
0 Disabled
1 0
A
1 Enabled
d4-02 0299h Trim Control Lvl
0 ~ 100 %
1% 10%
A
E1-01 0300h
Input Voltage
155 ~ 255 VAC
1 VAC
240 VAC
A
KVA*
o2-09*
E1-03 0302h
V/F Selection
0h 50
Hz
1 0Fh
A
1h
60 Hz Saturation
2h
50 Hz Saturation
3h 72
Hz
4h
50 Hz VT1
5h
50 Hz VT2
6h
60 Hz VT1
7h
60 Hz VT2
8h
50 Hz HST1
9h
50 Hz HST2
Ah
60 Hz HST1
Bh
60 Hz HST2
Ch 90
Hz
Dh 120
Hz
Eh 180
Hz
Fh Custom
V/F
10h
Custom w/o limit
E1-04 0303h Max Frequency
0.0 ~ 200.0 Hz
0.1 Hz
60.0 Hz
A E1-03*
E1-05 0304h
Max Voltage
0.0 ~ 255.0 VAC (200/240VAC drives)
0.0 ~ 555.0VAC (400/480VAC drives)
0.1 VAC 240.0 VAC
A
E1-03*
kVA
o2-09*
E1-06 0305h Base Frequency
0.0 ~ 200.0 Hz
0.1 Hz
60.0 Hz
A E1-03*
E1-07 0306h Mid Frequency A
0.0 ~ 200.0 Hz
0.1 Hz
3.0 Hz
A E1-03*
E1-08 0307h
Mid Voltage A
0.0 ~ 255.0 VAC (200/240VAC drives)
0.0 ~ 555.0VAC (400/480VAC drives)
0.1 VAC 13.0 VAC
A
E1-03*
kVA
E1-09 0308h Min Frequency
0.0 ~ 200.0 Hz
0.1 Hz
1.5 Hz
A E1-03*
E1-10 0309h
Min Voltage
0.0 ~ 255.0 VAC (200/240VAC drives)
0.0 ~ 555.0VAC (400/480VAC drives)
0.1 VAC
9.0 VAC
A
E1-03*
kVA
E1-11 030Ah Mid Frequency B
0.0 ~ 200.0 Hz
0.1 Hz
0.0 Hz
A E1-03*
E1-12 030Bh
Mid Voltage B
0.0 ~ 255.0 VAC (200/240VAC drives)
0.0 ~ 555.0VAC (400/480VAC drives)
0.1 VAC
0.0 VAC
A
E1-03*
kVA
E1-13 030Ch
Base Voltage
0.0 ~ 255.0 VAC (200/240VAC drives)
0.0 ~ 555.0VAC (400/480VAC drives)
0.1 VAC 240.0 VAC
A
E1-03*
kVA
E2-01 030Eh Motor Rated FLA
0.1 ~ 1500.0 A
0.1 A 14.0
A
A kVA*
E2-02 030Fh Motor Rated Slip
0.0 ~ 20.0 Hz
0.01 Hz
3.3 Hz
F
kVA*
E2-03 0310h No-Load Current
0.0 ~ 1500.0 A
0.1 A 4.5
A
A kVA*
E2-05 0312h
Term Resistance
0.0 ~ 65.0 Ohm 0.001
Ohm 0.771 Ohm
A kVA*
E2-10 0317h Tcomp Iron Loss
0 ~ 65535 W
1 W
0 W
F
E2-11 0318h Mtr Rated Power
0.0 ~ 650.0 kW
0.01 kW
0.4 kW
F
F6-01 03A2h Comm Bus Flt Sel
0
Ramp to Stop
1 0
A
1 Coast
to
Stop
2 Fast-Stop
3 Alarm
Only
F6-02 03A3h
EF0 Detection
0 Always
Detected
1 0
A
1
Only During Run
F6-03 03A4h EF0 Fault Action
0
Ramp to Stop
1 1
A
1 Coast
to
Stop
2 Fast-Stop
3 Alarm
Only
F6-05 03A6h
0 ~ 1
1 0
A
Содержание CIMR-E7U Series
Страница 1: ...E7 Drive Parameter Access Technical Manual Drive Models CIMR E7U Document Number TM E7 11...
Страница 2: ......
Страница 6: ...iv This page intentionally left blank...
Страница 8: ...Connections 1 2 This page intentionally left blank...
Страница 10: ...Connections 1 4 This page intentionally left blank...
Страница 19: ...Connections 1 13 This page intentionally left blank...
Страница 21: ...Message Formats 2 2 This page intentionally left blank...
Страница 35: ...Troubleshooting 3 2 This page intentionally left blank...
Страница 43: ...Troubleshooting 3 10 This page intentionally left blank...
Страница 45: ...E7 Drive Parameters 4 2 This page intentionally left blank...
Страница 71: ...E7 Drive Parameters 4 28 This page intentionally left blank...
Страница 73: ...User Notes 5 3 This page intentionally left blank...
Страница 81: ...User Notes 5 11 Notes Enter the current application parameter data and any relevant notes...