Connections 1-9
■
RTS Control – H5-07
This parameter determines whether RTS is continually asserted (disabled) or asserted only during send (enabled). RTS must be enabled for
use with RS422/485 communications. The default is disabled (0).
Table 1.4 – RTS – Parameter H5-07
Value
Description
0
Disable (always ON)
1
Enable (ON only during send)
■
Communication Method – H5-08
This parameter determines which communication protocol is used. This manual deals with the Memobus (MODBUS RTU) protocol. The
default values is Memobus (0).
Table 1.5 – RTS – Parameter H5-08
Value
Description
0 Memobus(Modbus)
1 N2
(Metasys)
2 FLN
(APOGEE)