E7 Drive Parameters 4-17
Prm
Adr
Function
Data
Limits / Selections
Inc
Default
Run Acs
Dep
H5-01 0425h Serial Comm Adr
0h ~ 20h
1 1fh
A
H5-02 0426h
Serial Baud Rate
0 1200
Baud
1 3
A
1 2400
Baud
2 4800
Baud
3 9600
Baud
4 19200
Baud
H5-03 0427h
Serial Com Sel
0 No
Parity
1 0
A
1 Even
Parity
2 Odd
Parity
H5-04 0428h
Serial Fault Sel
0
Ramp to Stop
1 3
A
1 Coast
to
Stop
2 Fast-Stop
3 Alarm
Only
4
Run at D1-04
H5-05 0429h
Serial Flt Dtct
0 Disabled
1 1
A
1 Enabled
H5-06 042Ah Transmit WaitTIM
5 ~ 65 ms
1 ms
5 ms
A
H5-07 042Bh
RTS Control Sel
0 Disabled
1 1
A
1 Enabled
H5-08 0434h
Protocol Select
0 Memobus(Modbus)
1 0
A
1 N2
(Metasys)
2 FLN
(APOGEE)
H5-09 0435h
CE Detect Time
0.0 ~ 10.0 Sec
0.1 Sec
2.0 Sec
A
L1-01 0480h MOL Fault Select
0 Disabled
1 1
A
1
Std Fan Cooled
L1-02 0481h MOL Time Const
0.1 ~ 20.0 min
0.1 min
8.0 min
A o2-09*
L1-03 0482h Mtr OH Alarm Sel
0
Ramp to Stop
1 3
A
1 Coast
to
Stop
2 Fast-Stop
3 Alarm
Only
L1-04 0483h Mtr OH Fault Sel
0
Ramp to Stop
1 1
A
1 Coast
to
Stop
2 Fast-Stop
L1-05 0484h
Mtr Temp Filter
0.0 ~ 10.0 Sec
0.01 Sec
0.2 Sec
A
L2-01 0485h PwrL Selection
0 Disabled
1 2
A
o2-09*
1 PwrL
RideThru
t
2
CPU Power Active
L2-02 0486h
PwrL Ridethru t
0.0 ~ 25.5 Sec
0.1 Sec
0.1 Sec
A kVA*
L2-03 0487h PwrL Baseblock t
0.1 ~ 5.0 Sec
0.1 Sec
0.5 Sec
A kVA*
L2-04 0488h PwrL V/F Ramp t
0.0 ~ 5.0 Sec
0.1 Sec
0.3 Sec
A kVA*
L2-05 0489h
PUV Det Level
150 ~ 210 VDC
1 VDC
190 VDC
A
L3-01 048Fh
StallP Accel Sel
0 Disabled
1 1
A
1 General
Purpose
2 Intelligent
L3-02 0490h
StallP Accel Lvl
0 ~ 200 %
1% 120%
A
L3-03 0491h
StallP CHP Lvl
0 ~ 100 %
1%
50%
F
L3-04 0492h
StallP Decel Sel
0 Disabled
1 1
A
1 General
Purpose
2 Intelligent
3 Stall
prev
w/R
L3-05 0493h
StallP Run Sel
0 Disabled
1 1
A
1
Decel Time 1
2
Decel Time 2
L3-06 0494h
StallP Run Level
30 ~ 200 %
1% 120%
A
L3-07 0495h
StallP Gain
0.1 ~ 2.0
0.01
1
F
L3-08 0496h
StallP Intg Time
10 ~ 250 ms
1 ms
100 ms
F
L3-09 0497h
Decel Time Coef
1.0 ~ 5.0
0.1
1
F
L3-10 0498h
StallP Decel Lvl
80 ~ 95 %
1%
92%
F
L4-01 0499h
Spd Agree Level
0.0 ~ 200.0 Hz
0.1 Hz
0.0 Hz
A
L4-02 049Ah Spd Agree Width
0.0 ~ 20.0 Hz
0.1 Hz
2.0 Hz
A
L4-05 049Dh
Ref Loss Sel
0 Stop
1 1
A
1 Run@
80%
PrevRef
L4-06 04C2h
Fref at Floss
0.0 ~ 100.0 %
0.10% 80.00%
A
L5-01 049Eh
Num of Restarts
0 ~ 10
1 0
A
L5-02 049Fh
Restart Sel
0
No Flt Relay
1 0
A
1
Flt Relay Active
L5-03 04A0h Max Restart Time
0.5 ~ 180.0 Sec
0.1 Sec
180.0 Sec
A o2-09*
L5-04 04C3h Restart Mode Sel
0
Wait Time Mode
1
0
F o2-09*
1
Max Time Mode
Содержание CIMR-E7U Series
Страница 1: ...E7 Drive Parameter Access Technical Manual Drive Models CIMR E7U Document Number TM E7 11...
Страница 2: ......
Страница 6: ...iv This page intentionally left blank...
Страница 8: ...Connections 1 2 This page intentionally left blank...
Страница 10: ...Connections 1 4 This page intentionally left blank...
Страница 19: ...Connections 1 13 This page intentionally left blank...
Страница 21: ...Message Formats 2 2 This page intentionally left blank...
Страница 35: ...Troubleshooting 3 2 This page intentionally left blank...
Страница 43: ...Troubleshooting 3 10 This page intentionally left blank...
Страница 45: ...E7 Drive Parameters 4 2 This page intentionally left blank...
Страница 71: ...E7 Drive Parameters 4 28 This page intentionally left blank...
Страница 73: ...User Notes 5 3 This page intentionally left blank...
Страница 81: ...User Notes 5 11 Notes Enter the current application parameter data and any relevant notes...