E7 Drive Parameters 4-4
Simultaneous Broadcast Registers (Write only)
Simultaneous Broadcast Registers are those registers used to control the simultaneous operation of multiple devices either through a network
interface (option card) or via serial communications. These registers are available during drive RUN.
The “Addr” column contains the register address in hexadecimal format. Drive registers are always referenced in hexadecimal format. The
“Function” column contains the register name. The “Bit” and “Description” columns contain the list of available bits for that register and a short
description of each. If the “Bit” column is empty, the register contains word data and individual bits are meaningless.
Table 4.2 – Simultaneous Broadcast Registers (Write only)
Addr
Function
Bit
Description
0000h Reserved
Reserved
0001h Command
0h
0 = Stop 1 = Run
1h
0 = Forward 1 = Reverse
2h
3h
4h
5h
Multi-Function Input 1 @ S3 (default = External Fault) Function set by setting of H1-01
6h
Multi-Function Input 2 @ S4 (default = Fault Reset) Function set by setting of H1-02
7h
8h
9h
Ah
Bh
Ch
Multi-Function Input 3 @ S5* Function set by setting of H1-03
Dh
Multi-Function Input 4 @ S6* Function set by setting of H1-04
Eh
Multi-Function Input 5 @ S7* Function set by setting of H1-05
Fh
Reserved
0002h Frequency
Reference
30000/100%**
Note:
*
Use of these bits is dependent on the setting of register 0Fh bits 0Ch, 0Dh and 0Eh. Refer to
Table 4.1 – Command Registers (Read / Write).
**
This value must be sent to the drive as a hexadecimal value. Example: 4096 = 1000h.
The scaling is fixed at 30000/100%. and is not affected by parameter o1-03.
It is affected by the maximum frequency of the drive receiving the command. Simply it is ((decimal freq ref)/30000)* (drive’s maximum frequency).
Example: Send 1000h to drive. 1000h = 4096 decimal.
(4096*100%)/30000
=
13.65%.
If drive’s maximum frequency is 60Hz, then the frequency reference command to the drive is 60*13.65% or 8.19Hz.
Содержание CIMR-E7U Series
Страница 1: ...E7 Drive Parameter Access Technical Manual Drive Models CIMR E7U Document Number TM E7 11...
Страница 2: ......
Страница 6: ...iv This page intentionally left blank...
Страница 8: ...Connections 1 2 This page intentionally left blank...
Страница 10: ...Connections 1 4 This page intentionally left blank...
Страница 19: ...Connections 1 13 This page intentionally left blank...
Страница 21: ...Message Formats 2 2 This page intentionally left blank...
Страница 35: ...Troubleshooting 3 2 This page intentionally left blank...
Страница 43: ...Troubleshooting 3 10 This page intentionally left blank...
Страница 45: ...E7 Drive Parameters 4 2 This page intentionally left blank...
Страница 71: ...E7 Drive Parameters 4 28 This page intentionally left blank...
Страница 73: ...User Notes 5 3 This page intentionally left blank...
Страница 81: ...User Notes 5 11 Notes Enter the current application parameter data and any relevant notes...