Delayed Egress
7100, 7200 Series Exit Device
Installation Instructions
80-9470-0162-000 10/20
19
Wiring Diagram - 691F Electric Trim Control
Operation:
Fail Secure Trim allows access control for entry. Outside trim will remain locked during power failure
or fire alarm activation. (Figure 13)
Electric trim operation will not affect armed device.
Figure 13
20
Operating Instructions
Moment
a
ry/
Re
s
et
Byp
ass
/
M
a
int
a
ined
LHR
S
hown
Figure 14
There are three (3) modes of operation (Figure 14):
• Delayed Egress
• Momentary Egress
• Bypass (Maintained) Egress
Delayed Egress Mode
1.
Apply power to device. The initialization / self test sequence is as
follows:
•
Cover LED is RED for 2 seconds with horn sounding for 500ms.
•
Cover LED is then GREEN for 2 seconds, followed by AMBER for 1
second with the 4 diagnositc LEDs illuminated.
•
Cover LED is RED and green diagnostic LED is illuminated. The device is now armed, which
will not allow pushpad to retract latchbolt for immediate egress.
2.
If the device is not functioning, refer to the Troubleshooting Guide.
Momentary Egress Mode (Figure 14)
1.
With device armed, rotate key counter clockwise and return to center position (remove key).
2.
Red LED will flash quickly, approximately two times every second. Device will release for momentary egress
for 10 seconds (factory set). 5, 10, 20 or 40 second reset delay may be selected using DIP switch positions
4 and 5.
3.
After the reset delay time has elapsed, or if the cylinder key is rotated a second time counter clockwise
during a reset delay, the device shall re-arm. When an external DPS is used and door is opened and closed
during momentary egress, the selected reset delay shall be canceled and the device shall re-arm.
4.
Device will now be back in delayed egress mode.