Delayed Egress
7100, 7200 Series Exit Device
Installation Instructions
80-9470-0162-000 10/20
Note:
New wiring shown.
Items followed by * indicate NEW PCBA wiring OR NEW DEVICE wiring that differs from Legacy wiring. Pluggable
4-pin connections from Device Harness to Main Harness is for new QC12 hinge wiring method.
QC12 Hinge -
Wiring Options
Wiring to 8-pin and 4-pin connectors are REQUIRED (12 wires max)
- If external DPS wiring is REQUIRED (Set PCBA Dip Switch S2-7 OFF)
- If LBM, Trim Monitor, OR Electrified Trim Options are REQUIRED.
10
ElectroLynx Wiring Options Overview with QC12 Hinge
Refer to Figure 7 on page 14 for “O” Monitor - Trim Actuated SPDT Switch wiring.
NOTE:
•
Switch wiring max load: 2A @28VDC.
•
Wire must be protected from abrasion.
•
For use with Class II circuits only.
•
For ElectroLynx QC12 Hinge Connector System: Follow Sections 11, 12, and 13 wiring instructions.
•
For non-ElectroLynx door:
Remove connector at end of exit device and connect to incoming wires from power source using
wire nuts, butt splices, etc. See Section 14 for hole locations and sizes.
After routing two wires from ET through the chassis and the wire channel in back of rail then Install Molex Female
4-pin connector (supplied) onto pre-crimped female terminals ontoBlack wire pin 4-1, Red wire pin 4-2