Delayed Egress
Installation Instructions
7100, 7200 Series Exit Device
80-9470-0162-000 10/20
Resetting device from Bypass Mode to Delayed Egress Mode (Page 23, Figure 14)
1.
Rotate key counter clockwise, return to center position and remove.
2.
Solid red LED will illuminate.
3.
Device will be in delayed egress mode.
Delayed Egress Operation When Armed
Exit door is normally closed and latched. Delayed Egress device secures door in locked mode with solid red LED
indicating locked mode status. Depressing pushpad for three (3) seconds or less will sound device nuisance
beep without initiating alarm. Depressing pushpad longer than three (3) seconds will initiate an irreversible local
audible beeping tone (approximately two times every second) and a visual amber indicator. After delay time (15
or 30 seconds), device releases, LED changes to green, and siren changes to a steady tone which continues to
alarm until reset by keyswitch. Remote monitoring contact outputs can be used to alert security personnel. Person
depressing pushpad is denied egress for 15 or 30 seconds (depending upon setup) and security personnel are
alerted.
NOTE: 30 seconds may be accepted by local jurisdiction.
Re-arm After Closing for Indefinite Delay
With 40 second momentary egress setting (S2-4 ON & S2-5 ON), S2-8 ON, and an external DPS is wired to the
PCBA-after activation of momentary egress by cylinder key switch or external remote reset signal, if the Door/DPS
is open beyond 40 seconds, it will remain in momentary egress mode indefinitely and shall not enter alarm mode.
Then once the Door/DPS is closed, it will re-arm immediately. With (S2-4 ON & S2-5 ON) S2-8 OFF for same
scenario as above, the device will enter alarm mode after 40 seconds if the Door/DPS is still open. If Door/DPS is
closed before 40 seconds, it will re-arm immediately.
20
Operating Instructions, continued
21
Additional Options Non ElectroLynx Wiring
Or
a
nge
White
Green
NC
NO
C
T
a
n
Gr
a
y
Pink
NC
NO
C
Figure 8
Latchbolt Monitor
Switch
“S” Suf
fi
x
O Suffix
Outside Trim Monitor Switch is a SPDT switch that monitors trim lever.
Electrically Controlled Trim (Mortise Device) “Safe/Secure”
The Delayed Egress Exit Device is available with Fail Safe or Fail Secure
outside trim operation. In a fire condition, the Fail Safe trim will release for
entry. When Access control is used, the Fail Secure trim allows entry by
means of a remote card reader, keyswitch, push button, etc.
Note: If a Door Position Switch is not used, the trim will open the door
without affecting the device in an armed condition (refer to wiring diagrams for
wiring).
This option is used when outside trim is desired to be used with an external
Door Position Switch (by others). This switch will allow bypass (disarms
device) when the trim is used for ingress. The device will need to be reset
upon entry by means of the keyswitch on the device or a remote SPDT switch
(refer to wiring diagrams for wiring).
Outside Trim Monitor
Switch
“O” Suf
fi
x
Figure 9
Bypass (Maintained) Egress Mode (Figure 14)
1.
Rotate key clockwise, return key to center position and remove.
2.
Red LED will flash slowly (one time every four seconds).
3.
Device is disarmed, acting as a standard exit device which allows free egress.