Revision 1.1
WebSwitch™ Users Manual
Input Control Option (Model XRDI-WS3P only)
The inputs can be configured to control the outlet. The options in this drop down menu are used to
specify if and how the input affects the outlet, and are described below. Note that in all cases, input
changes will only affect the outlet at the time the input is changed. Once the change has taken place
the state of the input has no effect on the state of the outlet. In other words, if the input causes the
outlet to go on, a user may turn the outlet off from the web browser, even if the input is still on.
-
no outlet control
:
The input has no effect on the outlet.
-
set outlet equal input 1
:
When the input is tied to ground, the outlet turns
on
. When the input
is open, the outlet turns
off
.
-
set outlet opposite of input 1
:
When the input is tied to ground, the outlet turns
off
. When the
input is open, the outlet turns
on
.
-
latch outlet when input 1 on (reset via web)
:
When the input is tied to ground, the outlet turns
on
. Once the outlet is
on,
it will stay
on
(unaffected by input change) until it is turned
off
manually via the web (or command) by a user or WebSwitch Plus™ is powered off. This option
is useful for alarming functions.
-
latch outlet when input 1 off (reset via web)
:
When the input is open, the outlet turns
on
.
Once the outlet is
on,
it will stay
on
(unaffected by input change) until it is turned
off
manually
via the web (or command) by a user or WebSwitch Plus™ is powered off. This option is useful
for alarming functions.
-
latch outlet when input 1 changes (reset via web)
:
Each time the input is tied to ground or
when the input is open, the outlet turns
on
. Once the outlet is
on,
it will stay
on
(unaffected by
input change) until it is turned off via the web (or command) by a user or WebSwitch Plus™ is
powered off. This option is useful for alarming functions.
-
toggle outlet when input 1 on
:
When the input is tied to ground, the outlet will change states.
When the input is open, the outlet will remain in its current state.
-
toggle outlet when input 1 off:
When the input is open, the outlet will change states. When
the input is tied to ground, the outlet will remain in its current state.
-
toggle outlet when input 1 changes
:
Each time the input is tied to ground, or open, the outlet
will change states.
-
pulse/reboot outlet when input 1 on
:
When the input is tied to ground, the outlet will pulse for
the Pulse/Reboot Time specified. The input may stay tied to ground and the pulse time will not
be affected. If the input is tied to ground, opened, and then tied to ground again, before the end
of the pulse time, the Pulse Duration timer will be restarted (it will re-start each time the input is
tied to ground) and the outlet will continue to remain
on
until the timer expires.
-
pulse/reboot outlet when input 1 off
:
When the input is open, the outlet will pulse for the
Pulse/Reboot Time specified. The input can remain open and the pulse time will not be affected.
If the input is tied to ground and re-opened before the end of the pulse time, the Pulse Duration
timer will be re-started (it will re-start each time the input is open) and the outlet will continue to
remain
on
until the timer expires.
-
pulse/reboot outlet when input 1 changes:
Each time the input is tied to ground or opened,
the outlet will pulse for the Pulse/Reboot Time specified. If the state of the input changes before
the end of the pulse, the timer will be re-started (it will re-start each time the input changes) and
the outlet will continue to remain
on
until the timer expires.
Pulse/Reboot Time
When WebSwitch™ receives a pulse command for the outlet (through the web page or the
command interface), the outlet will pulse for the time specified in this field. Note that when a pulse
command is sent through the command interface, the command can include a pulse time which will
over-ride this value (for that pulse only). The time is specified in seconds and can range from
0.1
seconds to
86400
seconds in 0.1 second increments. Default time is
1.5
seconds.