Basic Installation Procedures
975-0998-01-01
25
Series Stacking
A series stacking configuration allows two inverters to be configured to produce 120 and 240 VAC, also known as, a single-phase
three-wire configuration. For example, a Freedom EX 4000 can be installed as
L1
while another Freedom EX 4000 operates as
L2
.
However, it is important to remember that for series stacking configuration, only
AC IN L1
|
AC OUT L1
terminals should be used
and that the
AC IN L2
|
AC OUT L2
terminals must have no connections at all. If
L2
is connected to any incoming or outgoing AC
line, the inverter/charger may suffer internal damage not covered by warranty.
NOTICE
GENERAL PRECAUTIONS
n
Contact Xantrex prior to stacking two Freedom EX 4000 units together. Stacking configuration via USB is a required step to
enable stacking.
n
Install stacked Freedom EX 4000s in close proximity to each other.
n
Connect RJ45 CAT5e/6 straight-through network cables to each inverter’s Sync port as well as the RV-C ports shown in
below.
n
Do not connect any wires to the
AC IN L2
|
AC OUT L2
terminals on both units at all when stacking.
n
Each inverter must be enabled and turned on individually before AC power becomes available.
Failure to follow these instructions can result in equipment damage and may void the warranty.
Figure 11 Series Stacking Using Two Freedom EX 4000s
N
L1
L2 G
N
L1
L2 G
AC IN
AC OUT
N
L1
L2 G
N
L1
L2 G
AC IN
AC OUT
B
E
SHORE
NEUTRAL BUS
INVERTER
NEUTRAL BUS
BUS
COMMON
BUS
COMMON
20A
20A
20A
20A
SHORE
INVERTER LOAD
A
C
D
G
F
c
For illustration purposes only. Not all electrical connections are shown.
The □ icon is a circuit-breakered main line connection to the line bus.
A
RV AC Disctribution panels with AC
breakers for shore and inverter load
(downstream) circuits
E
Second Freedom EX 4000
B
First Freedom EX 4000
F
AC output cable with individual wire L
connected to the inverter's L1 terminal
and to the inverter load sub-panel's 50A
L2 pole. Also jointly connects to a 20A
pole.
C
AC output cable with individual wire L
connected to the inverter's L1 terminal
and to the inverter load sub-panel's 50A
L1 pole. Also jointly connects to a 20A
pole.
G
AC input cable with individual wire L
connected to the inverter's L1 teminal
and to the shore panel's 50A L2 pole.
D
AC input cable with individual wire L
connected to the inverter's L1 teminal
and to the shore panel's 50A L1 pole.
c
Do not connect to the inverter’s L2
terminals in both units.
NOTICE
EQUIPMENT DAMAGE
Do not connect any wires to the
AC IN L2
|
AC OUT L2
terminals on both units at all when series
stacking.
Failure to follow these instructions can result in equipment damage and may void the warranty.