Original Operating Instructions
BATD0100-ES-1-480-1 (Outdoor)
Decommissioning
O_BATD0100-ES-1-480-1_(Outdoor)_V2.2_US
Page
103
of
110
10 Decommissioning
Procedure:
1.
Stop
the product (Section 7.4).
2.
Switch off
the AC/DC voltage externally and
secure
it from being
switched on again.
3.
Ensure
that the product is de-energized.
4.
Disconnect
the AC/DC cables.
5.
Ensure
that the AC/DC cables are permanently de-energized.
6.
Ensure
that no residual voltage is still present within the DC link by
means of suitable testing equipment (Figure 11).
7.
Ensure
that no residual voltage is still present within the harmionic filter
by means of suitable testing equipment (Figure 12).
8.
Switch off
voltage measuring and supply voltage (Section 10.1) and
disconnect
the lines.
9.
Ensure
that the lines for supply voltage are permanently de-energized.
10.
Disconnect
Ethernet cable and any other connected cables and lines.
10.1 Disconnecting Voltage Measurement and Supply Voltage
By switching the motor protecting switch (-F31) in position
O
, the voltage
measurement is disconnected from the grid (Figure 11).
The supply voltage is connected from outside and can be disconnected by
means of an external fusing.