Original Operating Instructions
BATD0100-ES-1-480-1 (Outdoor)
Installation
O_BATD0100-ES-1-480-1_(Outdoor)_V2.2_US
Page
73
of
110
Procedure:
1.
Route
the cable through the cable entry grommet.
2.
Connect
the cables as shown in Figure 25.
3.
Lead
the cable downwards at the inner side of the cabinet.
4. If necessary,
fix
the cables with cable straps.
5.5.1.6 Option Island Grid Function
If the product has the island grid function, an external voltage (+24 V
DC
) must be
applied on the terminals (-X17.1-2) so that the product can also operate parallel
to the grid. By disconnecting the external voltage via an external disconnecting
device, the product can establish an island grid.
The terminals (-X17.1-2) are implemented as a potential-free feedback contact.
A signal on this feedback contacts manage the switching in and out of the island
grid mode.
Figure 26: Cable routing to terminal strip (-X17)
Figure 27: Wiring diagram extract
terminal strip (-X17)
Procedure:
1.
Locate
terminal strip (-X17) (Figure 26).
2.
Open
the corresponding cable ducts.
3.
Route
the cable through the cable entry grommet.
4.
Connect
power supply (+24 V
DC
) (Figure 27):
o
DC (+) to terminal (-X17.1)
o
DC (-) to terminal (-X17.2)
5.
Close
the cable ducts.
6.
Fix
the cable with cable clamps.