Original Operating Instructions
BATD0100-ES-1-480-1 (Outdoor)
Appendix
O_BATD0100-ES-1-480-1_(Outdoor)_V2.2_US
Page
108
of
110
13.2.1 Electrical Data
Table 14: Electrical data
COMMENTS
GRID SIDE
Max. AC apparent power
(S
max
)
120 kVA (2 h)
At nominal grid voltage
Nominal AC power
(P
AC, nom
)
100 kW
At cos (
φ) = 1.0
Nominal grid voltage
(U
AC,nom
)
480Y / 277 V
Grid voltage range
+/- 10% of U
AC, nom
System type
Solidly grounded wye,
3 phase, 4 wire
Nominal grid frequency
(f
nom
)
60 Hz
Max. grid current (I
AC,max
)
144 A
Max. short circuit level
(I
AC, SC
)
35 kA
P
ower factor (cos φ)
> 0.98
At > 20 % of
nominal AC power
AC current distortion (THD)
< 3 %
DC SIDE
Nominal DC voltage
(U
DC, nom
)
750 V
DC voltage range
450 … 890 V
DC current range
+/- 266 A
Max. short circuit level
(I
DC, SC
)
5 kA / 40 kA (max. 1 ms)
Without DC fuses /
External protection
required
Independent DC sources
1
GENERAL
Control strategy
CC-CV,
power controlled
ISLAND GRID
Efficiency
(93.9|96.9|97.1|97.0|96.7) % At (10|30|50|75|100) %
power
Loss in standby at night
< 30 W
Max. auxiliary power
< 250 W
Excluding optional
heating
MEASURING ACCURACY
DC-voltage
1% of maximum DC voltage
AC-voltage
1% of nominal grid voltage
DC-current
1% of maximum DC current
AC-current
1% of rated current
Active power (AC)
2% of maximum AC power
Apparent power (AC)
2% of maximum AC power
Reactive power (AC)
2% of maximum AC power
Active power (DC)
2% of maximum DC power
Grid frequency
+/- 40 mHz
Average value of
8 grid periods