Manual 37353A
MFR 13 Packages - Protection Relay
© Woodward
Page 61/91
Changing the Relay Assignment
Change relay-
allocation? YES
Change relay assignment?
YES/NO
This parameter permits the user to change how the relay outputs are configured.
Refer to the list of parameters.
YES
.............. The relay assignments can be configured and the user may define the
relay functionality and assignments. The subsequent screens are dis-
played.
NO
................ The relays are configured with the factory default settings. The sub-
sequent screens are not displayed.
NOTE
All relay outputs are configured the same. The following is an example showing relays 1 through 3.
Depending on the model purchased, the unit may have up to 7 configurable relays. The
Packages GPX
/
GPX-I
/
GPY-I
/
GPY-I-N
/
K08
enable to use 4 additional relays.
Example:
Relay 1 to 3
Funct. relay 123
(R=releases) RRR
Function of the relays 1, 2, and 3
E/R
The individual relays may be configured as either E=Energizes (Normally Open
contacts) or R=Releases (Normally Closed contacts).
E
................... The relay is configured as normally open (N.O.) contacts. The relay
will energize only if the assigned monitoring function has tripped.
R
................... The relay is configured as normally closed (N.C.) contacts. The relay
is always energized and will only de-energize (release) if the as-
signed monitoring function has tripped.
NOTE
Relay 1 is configured as R (release/N.C.) and cannot be modified.