Manual 37353A
MFR 13 Packages - Protection Relay
© Woodward
Page 83/91
Pkg.
Parameter
Setting range
100/400 V version
Default setting
Customer setting
RELAYS
External Clearing
ON/OFF OFF
1
0
1
0
Auto-clearing relays
ON/OFF OFF
1
0
1
0
Release delay
Overvoltage
0.02 to 99.98 s
0.10 s
Release delay
Undervoltage
0.02 to 99.98 s
0.10 s
Release delay
Asymmetry
0.02 to 99.98 s
0.10 s
Release delay
Overfreq.
0.02 to 99.98 s
0.10 s
Release delay
Underfrq.
0.02 to 99.98 s
0.10 s
Release delay
Overcurr.
0.02 to 99.98 s
0.20 s
GP
/
K08
Release delay
Earth F.
0.02 to 99.98 s
0.20 s
Release delay
Overload
0.02 to 99.98 s
0.10 s
Release delay
Rev.Power
0.02 to 99.98 s
0.10 s
Release delay
Unb. Load
0.02 to 99.98 s
0.10 s
Release delay
react.cap.
0.02 to 99.98 s
0.10 s
Release delay
react.ind.
0.02 to 99.98 s
0.10 s
Auto-clearing Display
ON/OFF OFF
1
0
1
0
Clearing display
after
1 to 99 s
1 s
Change relay-
allocation
YES/NO NO
Y
N
Y
N
Funct. relay 12
E/R RE
Funct. relay 123
E/R REE
GPX
GPX-I
GPY-I
GPY-I-N
K08
Funct. relay 45
E/R EE
GPX
GPX-I
GPY-I
GPY-I-N
K08
Funct. relay 678
E/R EEE
Collect response
to relay
0 to 3/7
0002
Overvoltage 1
to relay
0 to 3/7
0002
Overvoltage 2
to relay
0 to 3/7
0002
Undervoltage 1
to relay
0 to 3/7
0002
Undervoltage 2
to relay
0 to 3/7
0002
Zero-voltage to
relay
0 to 3/7
0002
Asymmetry to
relay
0 to 3/7
0002
Overfrequency 1
to relay
0 to 3/7
0003
Overfrequency 2
to relay
0 to 3/7
0003
Underfrequency 1
to relay
0 to 3/7
0003
Underfrequency 2
to relay
0 to 3/7
0003
Overcurrent1 to
relay
0 to 3/7
0002
Overcurrent2 to
relay
0 to 3/7
0002
Overcurrent3 to
relay
0 to 3/7
0002
Current-Inv. to
relay
0 to 3/7
0002
GP
/
K08
Earth Fault 1
to relay
0 to 3/7
0003
GP
/
K08
Earth Fault 2
to relay
0 to 3/7
0003
Overload to
relay
0 to 3/7
0003
Reverse/min.pow. to
relay
0 to 3/7
0003
Unbalanced Load
to relay
0 to 3/7
0002
Ind. react.pow.
to relay
0 to 3/7
0002
Neg. react.pow.
to relay
0 to 3/7
0002
GPX-I
GPY-I
GPY-I-N
K08
Interface Fault
to relay
0 to 3/7
0002