Manual 37353A
MFR 13 Packages - Protection Relay
Page 80/91
© Woodward
Appendix E.
List of Parameters
Product number
P/N _____________________________ Rev ______________________________
Version MFR
13 ______________________________________________________________
Project _____________________________________________________________________
Serial number
S/N _______________
Date
_____________________________
Pkg.
Parameter
Setting range
100/400 V version
Default setting
Customer setting
BASIC DATA
Software version
- -
SPRACHE/LANGUAGE
German/English English
G
E
G
E
Enter code
0000 to 9999
-
Password Protection
ON/OFF ON
1
0
1
0
Define level 1
code
0000 to 9999
0001
Define level 2
code
0000 to 9999
0002
Direct parametr.
YES/NO NO
Y
N
Y
N
MEASUREMENT
Volt.-Measuring
Phase to phase / Phase-neutral
Phase-neutral
pn
pp
pn
pp
GP
/
K08
Volt.transformer secondary
50 to 125/50 to 480 V
100/400 V
GP
/
K08
Volt.transformer primary
00.100 to 65.000 kV
00.400 kV
GPX
GPX-I
GPY-I
GPY-I-N
Volt.transformer sec.(GN)
50 to 125/50 to 480 V
100/400 V
..
Volt.transformer prim(GN)
00.100 to 65.000 kV
00.400 kV
..
Volt.transformer sec.(MN)
50 to 125/50 to 480 V
100/400 V
GPX
GPX-I
GPY-I
GPY-I-N
Volt.transformer prim(MN)
00.100 to 65.000 kV
00.400 kV
Current transf.
1 to 9,999/{x} A
1,000/{x} A
GPX
GPX-I
GPY-I
GPY-I-N
K08
Rated voltage
5 to 125/10 to 480 V
100/400 V
GPX
GPX-I
GPY-I
GPY-I-N
K08
Rated frequency
40.0 to 70.0 Hz
50.0 Hz
Rated current
1 to 9,999 A
1,000 A
Rated power
5 to 32,000 kW
500 kW
Power measuring
one-phase/three-phase three-phase
s
t
s
t
CONTROL FUNCTIONS
GPX
GPX-I
GPY-I
GPY-I-N
K08
Synchronizing
ON/OFF ON
1
0
1
0
..
Synchronization df
max
0.02 to 0.49 Hz
0.18 Hz
..
Synchronization df
min
0.00 to -0.49 Hz
-0.10 Hz
..
Synchronization dV
max
0.1 to 15.0 %
6.0 %
..
Synchronization
Max phase <
1 to 60°
2°
..
Synchronization Time
pulse>
50 to 250 ms
200 ms
GPX
GPX-I
GPY-I
GPY-I-N
K08
Gen.circ.breaker Pick-up
t.
40 to 300 ms
80 ms