Manual 37353A
MFR 13 Packages - Protection Relay
Page 82/91
© Woodward
Pkg.
Parameter
Setting range
100/400 V version
Default setting
Customer setting
PROTECTION
Inv.time ov.curr
monitoring
ON/OFF ON
1
0
1
0
Inv.time char.
Normal / High / Extreme
Extreme
Inv.time ov.curr
Tp=
0.01 to 1.99 s
0.10 s
Inv.time ov curr
Ip=
0.1 to 3.0*In
1.0 * In
Inv.time ov.curr
I start=
1 to 3.00*In
1.00 * In
Inv.time ov.cur.
V-restr.
ON/OFF ON
1
0
1
0
Inv.time ov.curr
Knee curve
10 to 99 %
20 %
GP
/
K08
Earth current
monitoring
ON/OFF ON
1
0
1
0
..
Earth current 1
Response
10 to 300 %
120 %
..
Earth current 1
Delay.
0.02 to 99.98 s
0.1 s
..
Earth current 2
Response
10 to 300 %
160 %
..
Earth current 2
Delay
0.02 to 99.98 s
0.04 s
GP
/
K08
Earth current
Hysteresis
0 to 300 %
5 %
Overload Monitoring
ON/OFF ON
1
0
1
0
Overload Response
v.
0 to 150 %
120 %
Overload Delay
0 to 300 s
20 s
Overload Hysteresis
1 to 99 %
2 %
Reverse/min.pow. Monitoring
ON/OFF ON
1
0
1
0
Reverse/min.pow.
-99 to 99 %
-10 %
Reverse/min.pow. Delay
0.02 to 99.98 s
3.0 s
Reverse/min.pow. Hysteresis
1 to 99 %
2 %
Unbalanced load
Monitoring
ON/OFF ON
1
0
1
0
Unbalanced load
Response v.
0 to 100 %
20 %
Unbalanced load
Delay
0.02 to 99.98 s
0.25 s
Unbalanced load
Hysteresis
1 to 20 %
5 %
Reactive power
Monitoring
ON/OFF ON
1
0
1
0
Cap. react. pow.
Response v.
0 to 100 %
30 %
Cap. react. pow.
Delay
0.02 to 99.98 s
0.10 s
Ind. react. pow.
Response v.
0 to 100 %
30 %
Ind. react. pow.
Delay
0.02 to 99.98 s
0.10 s
React. pow. mon.
Hysteresis
1 to 20 %
2 %