Overload Monitoring
NOTE
All percentage values refer to a percentage of the configured rated power (page 37).
Function:
"Positive active load not within the permissible range"
The single-phase or three-phase active load is above the configured limit for overload. The message "
over-
load
" is displayed. This message can be suppressed with the discrete input "Blocking of protective device / re-
mote acknowledgement".
Overload
Monitoring ON
Overload monitoring
ON/OFF
ON
................ Overload monitoring is enabled. The subsequent screens of this func-
tion are displayed.
OFF
.............. Overload monitoring is disabled. The subsequent screens of this
function are not displayed.
Overload
Response v.000%
Threshold overload
0 to 150 %
The overload threshold is defined by this parameter. The percentage configured
here refers to the configured rated power (refer to page 37). If this limit is reached
or exceeded, the unit outputs the message "
overload
". If a relay was assigned to
this function in the relay manager, that relay will be energized.
Overload
Delay time 000s
Pickup delay
0 to 300 s
In order to initiate an overload alarm, the measured active load must exceed and
remain above the configured threshold without interruption for at least the period
of time specified in this screen.
Overload
Hysteresis 00%
Hysteresis for the overload monitoring
0 to 99 %
In order to prevent system fluctuations from continually initiating overload alarms,
a lower release point is defined here. If the control monitors the active load above
the permissible limit, the load must drop below the percentage of the rated load de-
fined here for the fault condition to be recognized as no longer existing.
Example: If a 100kW rated system has an overload limit of 120% (120kW) and a
hysteresis of 95% (95kW), the monitored load for an overload alarm must drop be-
low 95kW to reset the alarm.