Example:
analog output 2 (-20/0/4 to 20 mA: terminals 52/53)
Output of the wire-to-wire voltage L12:
20 mA-output
Analog output 2
0 .. 20 mA
Output range of the analog output 2
(20mA) -20..+20mA / 0..20mA / 4..20mA / OFF
The only variable that may be changed for this parameter is the lower value for this
analog output. The upper limit is 20 mA.
-20..20mA
.... -20 mA is the configured low limit for the analog output.
0..20mA
....... 0 mA is the configured low limit for the analog output.
4..20mA
....... 4 mA is the configured low limit for the analog output.
OFF
.............. The analog output is not enabled. The subsequent screens of this
function are not displayed.
Analog output 2
----------------
Output value of the analog output 2
The parameter that is to be assigned to the output is selected here (refer to Table
6-3).
Analog output
0mA = 00000V
Scaling of the lower output value
Defines the lower limit of the output.
Analog output
20mA = 00000V
Scaling of the upper output value
Defines the upper limit of the output.