Inverse Time-Overcurrent Monitoring
NOTE
All percentage indications of the current refer to the rated current (see page 37).
Function:
Monitoring of overcurrents including inversely proportional time dependent tripping characteristic.
The selected trip curve defines the tripping time according to the measured current. The tripping time will be de-
creased according to a defined curve the higher the measured current is. According to IEC 255 three different
characteristics are available.
Normal inverse:
]
[
*
1
)
/
(
14
.
0
02
.
0
s
t
I
I
t
p
P
−
=
Very inverse:
]
[
*
1
)
/
(
5
.
13
s
t
I
I
t
p
P
−
=
Extremely inverse:
]
[
*
1
)
/
(
80
2
s
t
I
I
t
p
P
−
=
Formula definitions:
t:
tripping time
t
p
time set point value
I
fault current / monitored current
I
n
rated (nominal) current
I
p
current set point value
If t is greater than 162 s the system trips at 162 s. If t is lower than t
min
the tripping time is t
min
. The reaction time
for t
min
depends on the time it takes to monitor the fault and the operating time of the relays. t
min
is at least 20 ms.
Please consider during configuration:
for I
start
: I
start
> I
n
and I
start
> I
p
for I
p
the smaller I
p
is, the steeper is the slope of the tripping curve