Manual 37353A
MFR 13 Packages - Protection Relay
Page 64/91
© Woodward
Analog Outputs (
Packages GPY-I
/
GPY-I-N
)
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
It is possible to configure a linear measuring range for each analog output and assign it to a specific measured
value (refer to table 6-3). The -20/0/4 to 20 mA analog outputs may be configured as a -20 to 20 mA, 0 to
20 mA, or 4 to 20 mA output. The user may define the upper and lower limits of the analog input measuring
range. Text may be assigned to the input as well.
Value
Lower and upper setting value
0 mA, 4 mA, -20 mA
20 mA
Vol 1
0 to 65,000 V
Vol 2
0 to 65,000 V
Vol 3
0 to 65,000 V
Vol ph-N AV
0 to 65,000 V
Vol ph-N max
0 to 65,000 V
Vol ph-N min
0 to 65,000 V
Vol 1-2
0 to 65,000 V
Vol 2-3
0 to 65,000 V
Vol 3-1
0 to 65,000 V
Vol ph-ph AV
0 to 65,000 V
Vol ph-ph max
0 to 65,000 V
Vol ph-ph min
0 to 65,000 V
Frequency
40.00 to 80.00 Hz
Current L1
0 to 9,999 A
Current L2
0 to 9,999 A
Current L3
0 to 9,999 A
Current AV
0 to 9,999 A
Current max
0 to 9,999 A
Current min
0 to 9,999 A
Direct. Cur 1
-9,999 to 9,999 A
Direct. Cur 2
-9,999 to 9,999 A
Direct. Cur 3
-9,999 to 9,999 A
Dir. Current AV
-9,999 to 9,999 A
Dir. Current max
-9,999 to 9,999 A
Dir. Current min
-9,999 to 9,999 A
Active power
-32,000 to 32,000 kW
Reactive power
-32,000 to 32,000 kvar
Apparent power
0 to 32,000 kVA
cosphi
i0.01 to 1.00 to c0.01
1
.... The sign of the current values is defined by the polarity of the
active component.
Table 6-3: Analog outputs, table of values