Manual 37353A
MFR 13 Packages - Protection Relay
Page 34/91
© Woodward
Direct Configuration
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
NOTE
A direct configuration cable DPC (P/N 5417-557), the LeoPC1 program (supplied with the cable) and the
corresponding configuration files are required to perform direct configuration. After the program has
been installed, consult the online help for a description of the PC program and its setup.
For configuration of the unit via PC program please proceed as follows:
•
Install the PC program on your laptop/PC according to the installation manual.
•
Before the end of the installation you are requested to select the language with which you want to start the PC
program. You can change the language at any time. The selection of the language refers only to language
with which the menus and subprograms of the PC program works. This setting will not change the language
of the control unit being configured.
•
After the installation of the PC program reboot your laptop/PC.
•
Establish the connection between your laptop/PC and the unit via the DPC. Plug one side to the configuration
plug of the unit and the other side to the COM1 port of your laptop/PC (other possibilities are described in the
installation manual).
•
You may start the PC program as follows:
- by "Start/Program/Woodward/LeoPC" (starting at version 3.1.xxx), or
- by a double click on a file ending ".cfg" in the subdirectory "LeoPC".
•
After the PC program has been started, establish the communication by pressing the "F2" button. This will es-
tablish a data link between the unit and the laptop/PC.
•
Start the sub program "Device Parameterization" and adjust the parameter of the unit to your application us-
ing this manual.
WARNING
If the following parameter "Direct parametr." is configured to "YES", communication via the interface
terminals X1 to X5 is disabled (
Packages GPX-I
/
GPY-I
/
GPY-I-N
/
K08
). If communication is to be re-
established via the interface terminals X1 to X5 after the unit is configured, the following parameter
must be set to "NO"!
Direct parametr.
YES
Direct configuration
YES/NO
YES
..............Configuration via the configuration port is enabled. The following
conditions must be met in order to carry out configuration via the di-
rect configuration cable:
- A connection must be established via the direct configuration cable
between the unit and the PC
- the Baud rate of the PC program must be set to 9,600 Baud
- the corresponding configuration file must be used (file name:
"xxxx-xxxx-yyy-zz.asm", initiated by xxxx-xxxx-yyy-zz.cfg)
NO
................Configuration via the direct configuration port is disabled.