No
Type
Description
14
Gen. reverse power
If reverse power detection is enabled, when the controller detects that the reverse
power value (power is negative) has fallen below the pre-set value and the action select
“Warn”, it will initiate a warning alarm.
15
Overload
If over power detection is enabled, when the controller detects that the over power value
(power is positive) has exceeded the pre-set value and the action select “Warn”, it will
initiate a warning alarm.
16
ECU warning alarm
If an error message is received from ECU via J1939, it will initiate a warning alarm.
17
Gen. loss of phase
If loss of phase detection is enabled, When controller detects the generator loss phase,
it will initiate a warning alarm.
18
Gen. phase rotation mismatch
When the controller detects a phase rotation error, it will initiate a warning alarm.
19
Breaker open/close fail
When the controller detects that the breaker close or open failure occurs, and the action
select “Warn”, it will initiate a warning alarm.
20
Temperature sensor wire break
When the controller detects that the temperature sensor is open circuit and the action
select “Warn”, it will initiate a warning alarm.
21
High temperature
When the controller detects that engine temperature has exceeded the pre-set value, it
will initiate a warning alarm.
22
Low temperature
When the controller detects that engine temperature has fallen below the pre-set value,
it will initiate a warning alarm.
23
Oil pressure sensor wire break
When the controller detects that the oil pressure sensor is open circuit and the action
select “Warn”, it will initiate a warning alarm.
24
Low oil pressure
When the controller detects that the oil pressure has fallen below the pre-set value, it
will initiate a warning alarm.
25
Fuel level sensor wire break
When the controller detects that the level sensor is open circuit and the action select
“Warn”, it will initiate a warning alarm.
26
Low fuel level
When the controller detects that the fuel level has fallen below the pre-set value, it will
initiate a warning alarm.
27
Analog input 4 Wire break
When the controller detects that the flexible sensor 1 is open circuit and the action
select “Warn”, it will initiate a warning alarm.
28
Analog input 4 High limit
When the controller detects that the sensor 1 value has exceeded the pre-set value, it
will initiate a warning alarm.
29
Analog input 4 Low limit
When the controller detects that the sensor 1 value has fallen below the pre-set value, it
will initiate a warning alarm.
30
Analog input 5 Wire break
When the controller detects that the flexible sensor 2 is open circuit and the action
select “Warn”, it will initiate a warning alarm.
31
Analog input 5 High limit
When the controller detects that the sensor 2 value has exceeded the pre-set value, it
will initiate a warning alarm.
32
Analog input 5 Low limit
When the controller detects that the sensor 2 value has fallen below the pre-set value, it
will initiate a warning alarm.
33
Discrete input xyz
When digit input port is set as warning and the alarm is active, it will initiate a warning
alarm.
34
GSM Communication fail
When select GSM enable but the controller couldn’t detect GSM model, controller sends
corresponding warning signal.
35
Ground fault
If earth fault detection is enabled, when the controller detects that the earth fault current
has exceeded the pre-set value and the action select “Warn”, it will initiate a warning
alarm.
4.1.3 Shutdown Alarms
When controller detects shutdown alarm, it will send signal to open
breaker and shuts down generator.
Appendix
Alarms and Warnings > Shutdown Alarms
37690A
easYgen-1800 | Genset Control
28
Содержание easYgen-1800
Страница 1: ...easYgen 1800 Operation Manual Genset Control easYgen 1800 37690A ...
Страница 10: ...General Information General Information Safety General Safety Notes 37690A easYgen 1800 Genset Control 10 ...
Страница 32: ...Appendix Alarms and Warnings Trip Alarms 37690A easYgen 1800 Genset Control 32 ...
Страница 36: ...37690A easYgen 1800 Genset Control 36 ...
Страница 37: ......