3.4.2 Stop engine after mains supplying load (again)
Mode
Energy
Breakers
Genset
AUTO
Mains is "abnormal"
GCB is closed
Running
Delivering power
MCB is open
Situation
n
Mains becomes normal so all of the parameters below meet
their well defined working ranges:
–
“Overvoltage”
–
“Undervoltage”
–
“Overfrequency”
–
“Underfrequency”
–
“Mains voltage asymmetry”
–
“Mains phase rotation fail”
Pre-Condition
The AUTO Stop procedure is going through sub procedures with
own timers.
If mains becomes abnormal during the process,
remaining with generator load has priority.
The remaining time of each of the timers initiated is
shown in the display.
When started via “Remote Stop (off Load)” input,
start procedures is the same as described below
but generator close relay is deactivated.
General notes
Operation
START/STOP Operation > Stop engine after mains su...
37690A
easYgen-1800 | Genset Control
22