No
Type
Description
1
Emergency stop
When the controller detects an emergency stop alarm signal, it will initiate a shutdown
alarm.
2
Overspeed
When the controller detects that the generator speed has exceeded the pre-set value, it
will initiate a shutdown alarm.
3
Underspeed
When the controller detects that the generator speed has fallen below the pre-set value,
it will initiate a shutdown alarm.
4
Loss of speed signal
When the controller detects that the engine speed is 0 and the action select “Shut‐
down”, it will initiate a shutdown alarm.
5
Gen. overfrequency
When the controller detects that the genset frequency has exceeded the pre-set value,
it will initiate a shutdown alarm.
6
Gen. underfrequency
When the controller detects that the genset frequency has fallen below the pre-set
value, it will initiate a shutdown alarm.
7
Gen. overvoltage
When the controller detects that the generator voltage has exceeded the pre-set value,
the controller will initiate a shutdown alarm.
8
Gen. undervoltage
When the controller detects that the genset voltage has fallen below the pre-set value, it
will initiate a shutdown alarm.
9
Fail to stop
If the engine does not fire after the pre-set number of attempts, it will initiate a shutdown
alarm.
10
Gen. overcurrent
When the controller detects that the genset current has exceeded the pre-set value and
the action select “Shutdown”, it will initiate a shutdown alarm.
11
Maintenance due
When count down time is 0 and the action select “Shutdown”, it will initiate a shutdown
alarm.
12
ECU shutdown alarm
If an error message is received from ECU via J1939, it will initiate a shutdown alarm.
13
ECU communication fail
If the module does not detect the ECU data, it will initiate a shutdown alarm.
14
Gen. reverse power
If reverse power detection is enabled, when the controller detects that the reverse
power value (power is negative) has fallen below the pre-set value and the action select
“Shutdown”, it will initiate a shutdown alarm.
15
Overload
If over power detection is enabled, when the controller detects that the over power
value (power is positive) has exceeded the pre-set value and the action select “Shut‐
down”, it will initiate a shutdown alarm.
16
Temperature sensor wire break
When the controller detects that the temperature sensor is open circuit and the action
select “Shutdown”, it will initiate a shutdown alarm.
17
High temperature
When the controller detects that engine temperature has exceeded the pre-set value, it
will initiate a shutdown alarm.
18
Oil pressure sensor wire break
When the controller detects that the oil pressure sensor is open circuit and the action
select “Shutdown”, it will initiate a shutdown alarm.
19
Low oil pressure
When the controller detects that the oil pressure has fallen below the pre-set value, it
will initiate a shutdown alarm.
20
Level sensor wire break
When the controller detects that the level sensor is open circuit and the action select
“Shutdown”, it will initiate a shutdown alarm.
21
Analog input 4 Wire break
When the controller detects that the flexible sensor 1 is open circuit and the action
select “Shutdown”, it will initiate a shutdown alarm.
22
Analog input 4 High limit
When the controller detects that the sensor 1 value has exceeded the pre-set value, it
will initiate a shutdown alarm.
23
Analog input 4 Low limit
When the controller detects that the sensor 1 value has fallen below the pre-set value, it
will initiate a shutdown alarm.
24
Analog input 5 Wire break
When the controller detects that the flexible sensor 2 is open circuit and the action
select “Shutdown”, it will initiate a shutdown alarm.
25
Analog input 5 High limit
When the controller detects that the sensor 2 value has exceeded the pre-set value, it
will initiate a shutdown alarm.
26
Analog input 5 Low limit
When the controller detects that the sensor 2 value has fallen below the pre-set value, it
will initiate a shutdown alarm.
27
Discrete input
When digit input port is set as shutdown and the alarm is active, it will initiate a shut‐
down alarm.
Appendix
Alarms and Warnings > Shutdown Alarms
37690A
easYgen-1800 | Genset Control
29
Содержание easYgen-1800
Страница 1: ...easYgen 1800 Operation Manual Genset Control easYgen 1800 37690A ...
Страница 10: ...General Information General Information Safety General Safety Notes 37690A easYgen 1800 Genset Control 10 ...
Страница 32: ...Appendix Alarms and Warnings Trip Alarms 37690A easYgen 1800 Genset Control 32 ...
Страница 36: ...37690A easYgen 1800 Genset Control 36 ...
Страница 37: ......