3.4.3 MANual START/STOP
Engine control is separated from breaker manage‐
ment. Breaker(s) must be manually opened/closed
(supply should be in normal range).
1.
Press MAN button
ð
the LED besides the button will illuminate to confirm the
operation
2.
Press START button to start the genset as described
above. With high temperature, low oil pressure, over speed
and abnormal voltage during generator running, controller
can protect genset to stop quickly.
Press can stop the running generator as described above.
3.5 Transition Procedures
3.5.1 Disconnect during Cranking
There are three conditions under control to abort starting the
engine:
n
speed sensor
n
generator frequency
n
engine oil pressure
They can be used separately or in combinations.
We recommend to select all three at the same time: engine oil
pressure together with speed sensor, and generator frequency.
This enables to separate immediately the starter motor from
engine. Additionally crank disconnect can be checked exactly.
When set as speed sensor, ensure that the number of flywheel
teeth is as same as setting.
Sensor not used? Make sure it is not selected!
Otherwise “start fail” or “loss speed signal” maybe
caused.
If speed sensor ( “Firing speed RPM” ) is not
selected: Rotating speed displayed in controller is
calculated by generator frequency and number of
poles.
If generator frequency ( “Firing speed Hz” ) is not
selected: Relative power quantity will neither be
collected not displayed (e.g. water pump applica‐
tion).
MANual Start
MANual Stop
Operation
Transition Procedures > Disconnect during Cranking
37690A
easYgen-1800 | Genset Control
24
Содержание easYgen-1800
Страница 1: ...easYgen 1800 Operation Manual Genset Control easYgen 1800 37690A ...
Страница 10: ...General Information General Information Safety General Safety Notes 37690A easYgen 1800 Genset Control 10 ...
Страница 32: ...Appendix Alarms and Warnings Trip Alarms 37690A easYgen 1800 Genset Control 32 ...
Страница 36: ...37690A easYgen 1800 Genset Control 36 ...
Страница 37: ......