HMI only! In ToolKit-SC frequency, speed, and oil pressure can be enabled/
disabled separately; HMI is using a table
“Firing speed” instead:
No.
Setting description
0
Gen frequency
1
Speed sensor
2
Speed Gen frequency
3
Oil pressure
4
Oil pr Gen frequency
5
Oil pr Speed sensor
6
Oil pr Speed Gen frequency
3.5.2 Manual Breaker Transition
When controller is in MANual mode, the procedures to switch
supply between mains and genset will start through manual
transfer process by pressing a breaker switch.
CAUTION!
Neither mains nor generator state is taken into
account. Breaker open/close works independent
from load.
If generator or mains are "out of range" load can
be damaged!
Both breakers GCB and MCB open:
Press breaker switch
ð
The according breaker will be closed.
Closing signal will last for the
“Closing time”
During this time all other breaker signals
are suppressed.
One of the breakers is closed - open this breaker.
Press breaker switch of the closed breaker
ð
The according breaker will be opened.
Opening signal will last for the
“Opening time”
During this time all other breaker signals
are suppressed.
Taking load
Unload
Operation
Transition Procedures > Manual Breaker Transition
37690A
easYgen-1800 | Genset Control
25
Содержание easYgen-1800
Страница 1: ...easYgen 1800 Operation Manual Genset Control easYgen 1800 37690A ...
Страница 10: ...General Information General Information Safety General Safety Notes 37690A easYgen 1800 Genset Control 10 ...
Страница 32: ...Appendix Alarms and Warnings Trip Alarms 37690A easYgen 1800 Genset Control 32 ...
Страница 36: ...37690A easYgen 1800 Genset Control 36 ...
Страница 37: ......