4 Appendix
4.1 Alarms and Warnings
4.1.1 Alarm Classes
Alarm class
Visible in the dis‐
play
LED and horn
Open GCB
Shut-down engine
Engine blocked
until acknowledge
Warn
X
X
This alarm does not interrupt the unit operation. An output of the centralized alarm occurs and the command
“Horn” is issued. Alarm text + flashing LED + Relay centralized alarm (horn)
Shutdown
X
X
Immediately
Immediately
X
With this alarm the GCB is opened immediately and the engine is stopped. Alarm text + flashing LED + Relay
centralized alarm (horn) + GCB open + Engine stop.
Trip/shut
x
x
Immediately
Cool down time
X
With this alarm the GCB is opened immediately and the engine is stopped after cool down. Alarm text +
flashing LED + Relay centralized alarm (horn) + GCB open + Cool down + Engine stop.
Trip
X
X
X
With this alarm the GCB is opened immediately but does not interrupt the unit operation. Alarm text + flashing
LED + Relay centralized alarm (horn) + GCB open.
Indication
X
This alarm does not interrupt the unit operation. A message output without a centralized alarm occurs. Alarm
text
4.1.2 Warnings
No
Type
Description
1
Overspeed
When the controller detects that the engine speed has exceeded the pre-set value, it
will initiate a warning alarm.
2
Underspeed
When the controller detects that the engine speed has fallen below the pre-set value, it
will initiate a warning alarm.
3
Loss of speed signal
When the controller detects that the engine speed is 0 and the action select “Warn”, it
will initiate a warning alarm.
4
Gen. overfrequency
When the controller detects that the genset frequency has exceeded the pre-set value,
it will initiate a warning alarm.
5
Gen. underfrequency
When the controller detects that the genset frequency has fallen below the pre-set
value, it will initiate a warning alarm.
6
Gen. overvoltage
When the controller detects that the generator voltage has exceeded the pre-set value,
the controller will initiate a warning alarm.
7
Gen. undervoltage
When the controller detects that the genset voltage has fallen below the pre-set value, it
will initiate a warning alarm.
8
Gen. overcurrent
When the controller detects that the genset current has exceeded the pre-set value and
the action select “Warn”, it will initiate a warning alarm.
9
Fail to stop
After “Stop solenoid hold” delay, if genset does not stop completely, it will initiate a
warning alarm.
10
Charge alternator low voltage
When the controller detects that charger voltage has fallen below the pre-set value, it
will initiate a warning alarm.
11
Battery undervoltage
When the controller detects that start battery voltage has fallen below the pre-set value,
it will initiate a warning alarm.
12
Battery overvoltage
When the controller detects that start battery voltage has exceeded the pre-set value, it
will initiate a warning alarm.
13
Maintenance due
When count down time is 0 and the action select “Warn”, it will initiate a warning alarm.
Appendix
Alarms and Warnings > Warnings
37690A
easYgen-1800 | Genset Control
27
Содержание easYgen-1800
Страница 1: ...easYgen 1800 Operation Manual Genset Control easYgen 1800 37690A ...
Страница 10: ...General Information General Information Safety General Safety Notes 37690A easYgen 1800 Genset Control 10 ...
Страница 32: ...Appendix Alarms and Warnings Trip Alarms 37690A easYgen 1800 Genset Control 32 ...
Страница 36: ...37690A easYgen 1800 Genset Control 36 ...
Страница 37: ......