Start and stop of the engine is managed with the same procedure
as in AUTO mode but without breaker control. Breakers can be
opened and closed without taking care of load, genset, or mains
state!
WARNING!
MANual breaker open/close request can destroy
the genset and/or substantial damage mains.
Take care for genset and supply.
3.3.3 Operation Mode STOP
In operation mode STOP breakers are open and engine is not run‐
ning.
This is a configurable operation mode, only. This is
NO emergency STOP!
3.4 START/STOP Operation
3.4.1 Start engine to supply load
Mode
Energy
Breakers
Genset
AUTO
Mains is "normal"
GCB is open
Not running
Ready for operation
MCB is closed
Situation
n
Mains becomes abnormal because one or more of the
parameters below misses its well defined working range:
–
“Overvoltage”
–
“Undervoltage”
–
“Overfrequency”
–
“Underfrequency”
–
“Mains voltage asymmetry”
–
“Mains phase rotation fail”
Pre-Condition
The AUTO Start procedure is going through sub procedures with
own timers.
General notes
General notes
Operation
START/STOP Operation > Start engine to supply load
37690A
easYgen-1800 | Genset Control
19